Installation; Emc-Compatible Control Cabinet Installation; Installation Instructions; Figure 10: Emc-Compatible Control Cabinet Installation - KEB COMBIVERT R6 Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

Installation

4.
Installation
4.1

EMC-compatible control cabinet installation

1
Main fuse
2
Main contactor
3
EMC side-mounted filter
(>=size 25 R-S or R6-N)
EMC sub-mounted filter
(<=size 19 R6-S)
4
If necessary, external voltage limi-
tation / synchronisation
5
Commutation reactor / harmonic
filter
6
COMBIVERT R6
7
if necessary, external DC fuses
8
Frequency inverter
9a
DC lines with
9b
Motor line with ferrite
10a
Equipotential bonding with the
housing earth
10b
Protective Earth (PE) on the
mounting plate power circuit
10c
Protective Earth (PE) on the
mounting plate control circuit
11
Mains connection power circuit
11 A Mains connection control circuit
12
Control lines
Large area contact at the mount-
ing plate
Figure 10:
4.2

Installation instructions

Warning
• Stationary install and earth COMBIVERT.
• The device must not be permeated by mist or water.
• Allow for sufficient heat dissipation if installed in a dust-proof housing.
Install the COMBIVERT in an appropriate housing in accordance with the local regulations
when operating it in explosion-endangered spaces.
• Protect COMBIVERT against conductive and aggressive gases and liquids.
• The lines of the R6-N commutation reactor must be limiting to 1m.
• The frequency inverter must be placed in the immediate environment of the R6-N.
26
ferriteDC-
EMC-compatible control cabinet installation
General installation instructions
12
150 mm
3
2
150 mm
1
5
11a
11
10a
150 mm
6
4
150 mm
7
10b
10c
8
30 mm
9a
9b