No.
Name
CP.18
ANOUT1 gain
The analog output displays the difference between actual supply frequency and set supply
frequency. At factory setting of CP.18 this corresponds to 1 V per 0.1 Hz difference. The dis-
play occurs with right sign. The reference value of 50 or 60 Hz is determined during power
on.
Setting range
0...±20,00
No.
Name
CP.19
DC switching level
This parameter determines the switching level for transistor output O1, as well as relay
output 2.
Setting range
0...3200.00 V
No.
Name
CP.20
general fault reset
Setting range
0
1...10
Setting
Meaning
The amplification to the desired output voltage can be
1.00
adapted with CP.18. Max. possible: ±10 V.
Setting
Meaning
The switching condition is fulfilled and the transistor
output is set if the DC voltage level exceeds the ad-
600.00 V
justed value in CP.19. Relay output 2 is set, if the load
shunt relay is additionally tightened.
A general fault reset can be activated with this parameter. At-
tention, the machine manufacturer must observe appropriate
protective measures for operating personnel and machine.
Setting
Meaning
No general fault reset.
Maximum errors, which are reset within one hour. If the
3
number of errors per hour exceeds the adjusted value
in CP.20, only a manual reset via the terminal strip can
be made.
Special adjustments
r/w
Enter
yes
r/w
Enter
yes
r/w
Enter
yes
based on
–
An.33
based on
–
LE.00
based on
–
Pn.15
47