KEB COMBIVERT R6 Instruction Manual page 49

Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

No.
Name
CP.33
operating mode
This parameter determines the master or slave of regenerative units at parallel connection.
Further it is adjusted whether a harmonic filter or a commutation choke is series-connected.
Single units must be adjusted to master.
Value range
0
1
2
3
4
5
No.
Name
CP.34
regeneration level
Value range
100...120 %
Meaning
Master with commutation reactor
Master with harmonic filter
Slave with commutation reactor
Slave with harmonic filter
Master-Slave with commutation reactor input selection
Master-Slave with harmonic filter input selection
Meaning
The regeneration level determines the starting value to energy regen-
eration. The adjusted value refers to the reference value of the DC
voltage in percentage. The status changes from Standby „Stb" to re-
generation „rEGEn".
Special adjustments
r/w
yes
r/w
yes
Enter based on
yes
Pn.19
Enter based on
cS.02
49