Siemens SIMOTION D4 5-2 Series Manual page 125

Hide thumbs Also See for SIMOTION D4 5-2 Series:
Table of Contents

Advertisement

Ambient conditions
The following conditions apply to modules that are shipped and stored in the original
packaging.
Table 6- 30
Parameter
Permissible ambient temperature
Atmospheric pressure
Permissible relative humidity
Installation altitude
Biological environmental conditions
Degree of protection according to EN 60529
(IEC 60529)
Pollution degree
Integrated drive control
Table 6- 31
Data
Max. number of axes for integrated drive
control (servo/vector/
SIMOTION D4x5-2
Manual, 02/2012
CX32-2 environmental requirements
Transport
Long-term storage
Operation
During transport and storage
During operation (condensation, icing, drip,
spray and splash water not permitted)
Storage
Transport
Operation
Controls for integrated drives
V
f
/
)
Supplementary system components
6.5 CX32-2 controller extension
Values
-40° C ... +70° C
-25° C ... +55° C
0° C ... +55° C up to 2000 m above sea level.
As of an altitude of 2000 m, the maximum
ambient temperature decreases by 7° C every
1000 m increase in altitude
620 ... 1060 hPa
10 % ... 100 %
5 % ... 90 %
Max. 4000 m above sea level.
For SINAMICS S120 drive components, see
SINAMICS Manuals.
Class 1B1 according to EN 60 721-3-1
Class 2B1 according to EN 60 721-3-2
Class 3B1 according to EN 60 721-3-3
IP20
2 according to EN 60 664-1
SIMOTION CX32-2
6 / 6 / 12 (alternative)
drive control based on SINAMICS S120 CU320-2,
firmware version V4.x
125