Siemens Synco ZW775 V2.0 Commissioning Instructions page 66

Central communication unit
Table of Contents

Advertisement

Message receiver 1...4
continued
66/148
Siemens Building Technologies
HVAC Products
Command sequence: Settings > Message receiver > Message receiver 1...4
Data point
Fault priority
Default val:
All
Setting val:
All, Only urgent
faults
Data point "E-mail address" is displayed if:
• Receiver type
• Interface
• Transmission protocol
Data point
E-mail address
Default val:
name@example.com
Setting val: E-mail address
Data points "Address ACS alarm" and "Port number ACS alarm" are displayed if:
• Receiver type
• Interface
• Transmission protocol
Data point
Address ACS alarm
Default val:
acs.example.com
Setting val:
Name / IP address
Port number ACS alarm
Default val:
49194
Setting val:
1...65535
Data points "Message repetition" and "Phone number receiver" are displayed if:
• Receiver type
• Interface
• Modem type
• Transmission protocol
Data point
Message repetition
Default val:
3
Setting val:
None, 1, 2, 3,
Unlimited
Phone number receiver
Default val:
(Blank)
Setting val:
Phone number
Commissioning instructions OZW775 V2.01
Parameterize OZW775
Explanation, example
Setting value "Only urgent faults" serves as a
filter when sending fault status messages.
= E-mail
= Ethernet
= SMTP
Explanation, example
The setting value (max. 20 characters) must
correspond to the e-mail address of the
receiver, e.g. PC/laptop with e-mail reception.
= ACS alarm
= Ethernet
= ACS protocol
Explanation, example
The setting value (max. 20 characters) must
correspond to the name or IP address of the
ACS alarm receiver, i.e. the PC/laptop with the
installed program "ACS Alarm".
The setting value must correspond to the port
number of program "ACS Alarm" ("ACS Alarm"
installed on PC/laptop).
= ACS alarm / mobile phone / fax / pager
= Modem
= Analog / ISDN / GSM
= ACS protocol / TAP / UCP / SMS GSM
Explanation, example
Setting value "None" attempts to send the
pending message once, and setting values "n"
(n = 1, 2, 3) attempt sending n+1 times.
The setting value corresponds to the phone
number of the receiver (e.g. mobile phone) that
is to receive messages (fault, maintenance
messages, system reports).
The default value (blank) means no default
phone number ex works.
Characters allowed: 0...9, /, -, w, W, =, @, !, &,
<, space and comma ' , '