Port Forwarding
Operate using
web browser
Operate using
1)
ACS software
Remote alarming
1)
ton ACS Alarm
1)
ACS File Transfer
Note
122/148
Siemens Building Technologies
HVAC Products
Configure the IP address of the web server OZW775 on one or several public ports. A
public port is the port used from the Internet.
The local port is the port for the web server OZW775. You cannot change this port, i.e.
the web server always uses port 80.
Internet data from the web browser are routed via public ports 8080 and 80 to IP
address 192.168.1.180 of the web server with port 80.
Public port: 8080, 80
Local port:
80
Public port: 50005
Local port:
50005
Public port: 49194
Local port:
49194
History File, Offline Trend
Public Port: 21
Local port:
21
1)
This function is supported from ACS CD V5.10. The DSL router can already be configured.
Local IP address
192.168.1.180  IP address of the web server OZW775 (central comm. unit).
Comment
OZW775
 Name to identify device.
The configured firewall services are activated automatically for "Local IP address".
Router SX763 does not need any other firewall settings.
Commissioning instructions OZW775 V2.01
Appendix
HTTP (web pages), data from Internet.
Web server port number.
ACS, data from Internet.
Web server port number.
ACS Alarm, data from Internet.
Web server port number.
1)
FTP (File Transfer Protocol), data from Internet.
Web server port number.