Page 1
Synco™ Central communication unit OZW775 V2.0 with integrated web server function Commissioning instructions Edition 2.01 Building Technologies CE1C5663en HVAC Products 22.06.2012...
Delete devices ....................42 3.2.4 Refresh device list ..................43 3.2.5 Refresh reference data points of devices ............44 Parameterize OZW775.................. 45 Parameterization using ACS ................. 45 3/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Table of contents 22.06.2012...
Page 4
Set the number of operating hours ..............96 5.4.5 Next report (system report) ................97 Final steps......................98 5.5.1 Check "Local" faults ..................98 5.5.2 Check "System" faults..................99 5.5.3 Delete history ....................100 4/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Table of contents 22.06.2012...
Page 5
Configure web server OZW775 ..............129 7.2.7 Free e-mail accounts ................... 131 7.2.8 Siemens router .................... 132 7.2.9 Terms and abbreviations on Ethernet and Internet ........133 Configuration diagrams ................139 Error code list for the central communication unit ........144 Data points (overview).................
Page 6
Blank page 6/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Table of contents 22.06.2012...
Only qualified persons trained by Siemens Building Technologies may commission Commissioning Synco products. Operation Only persons trained and instructed on potential risks by Siemens Building Technologies or its delegates may operate Synco products. Faults Contact service if the system is faulty and no trained person is available to diagnose and resolve the fault.
Flashing CF card is integrated or removed (after pressing button "long" on "Config"). 5 KNX (green/red) Dark No bus power supply. Steady green Bus power supply available. Flashing green Data exchange via KNX. Steady red Unit in addressing mode. 8/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Overview 22.06.2012...
Simultaneously press "Modem", "Ack", and "Config". Note: This resets all configuration data and settings. The device list and all unsent messages are deleted. History data is not deleted. 9/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Overview...
Refresh reference data points mean that the associated function is triggered immediately. If dots "…" follow commands such as Add device… , another context menu or dialog box opens. 10/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Overview 22.06.2012...
Page 11
Service, six of which are read- only and one is read/write. Example: End user Conversely, the end user has access only to three read-only data points in the Konnex operating page. 11/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Overview 22.06.2012...
Page 12
SMS Short Message Service SMTP Simple Mail Transfer Protocol Telocator Alphanumeric Protocol UCP Universal Computer Protocol Note See Section 7.2.9 for information on technical terms and abbreviations. 12/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Overview 22.06.2012...
First login via User name: Administrator Password: OZW775 2.5.3 Change password and language New password, new language. 2.5.4 Add user User name, password, language, user group. 13/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 14
Close the dialog box. ACS operation – [Edit device list] Select Applications > Popcard… to open the [Popcard] and check if the device list contains the device(s). 14/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 15
Paste Change the name of the parameter set Standard (1) (not mandatory). The parameter set Standard is ready for parameterization. 15/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 17
**) The command sequences Operating hours > Operating hours 1…5 (Hours run counter 1…5) and the corresponding data points are displayed only if e.g. data point "Input 5 = N.D5" was parameterized via Extra configuration > Operating hours". 17/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 18
Parameterization is not yet complete. Continue in application [ Popcard ] − "Commissioning mode = On". Applications [ Parameter Setting ] and [ Popcard ] display the same data points in − the "Settings" operating page. 18/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 19
Time to next message > Message receiver Test message receiver System report sent (read) > System report … Next report > Faults Delete history > Texts … Reset text 19/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 20
Modem message interval The time the central communication unit must wait between communication abortion − and reestablishing communication when connected via modem. 5.3.4 Error codes for modem communication 20/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 21
You need a DSL router with integrated DSL modem to connect to the Internet. DSL − (Digital Subscriber Line): Data transmission on traditional copper phone lines. The DNS server assigns domain names to IP addresses. DNS (Domain Name − System). 21/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 22
"ACS Alarm". Recommended commissioning finished Note Step 24 completes workflow "Recommended commissioning". The central communication unit or web server OZW775 are now ready for normal operation. 22/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Central communication units V1.0 with "Ethernet = No, Web server function = No" are (presumably) deployed already. If not, see the commissioning instructions C5663, Edition 1.0, dated December 6, 2005. 23/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
The central communication unit OZW775 comes with KNX device address 150. This address allows the central communication unit to send and receive data via the KNX bus, i.e. a new address can, but must not be set. 24/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Put cover back on. Note: Remember to turn on again AC 24 V operating voltage. xx:xx:xx:xx:xx:xx xx:xx:xx:xx:xx:xx xx:xx:xx:xx:xx:xx OZW775 OZW775 XXX HEX XXX HEX OZW775 25/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
(see document P3127). • The devices on the KNX network work smoothly, i.e. no red LEDs are on. • The clock time master on the KNX network is defined. 26/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
The latest ACS software must be installed on the PC/laptop. The central communica- tion unit comes with a CD to download the latest ACS software. You can also download the ACS software via the BT Global - INTRANET. https://intranet.sbt.siemens.com/sc-hvp/en/Downloads/ACS7.asp 27/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning...
ACS Service or ACS Operation Select the desired language and click Continue / Weiter Log in with the "Service" level password and click Log on 28/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Applications > Popcard > Device information > Central communication unit. From March 2008, the central communication unit V2.0 comes with "Software version Note V2.02" (firmware version). 29/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Do not switch off AC 24 V operating voltage while updating! Voltage interruption set an undefined state for the central communication unit OZW775 that only Siemens Building Technologies (HQ Zug, Switzerland) is able to undo. Update firmware See also the supplied installation instructions G5663xx (multi-lingual).
Push button "Config" >4 sec. and "CF Cards" light up Note: Keep the CF card in the upper slot "CF Card Memory" for web server operation. 31/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
You must change the user data after the first login. Security note The device will offer no access security if the default password is not changed. Siemens strongly recommends to change the default password directly after the first login. Workflow Select "User accounts"...
Select "User accounts" to open the window with the current users. Workflow Click to open a popup window. Enter the user name. Enter the password and repeat it. 33/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Page 34
Select the language. Select the user group. Click to confirm your entries. 34/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Recommended commissioning 22.06.2012...
Select Plant > New > Plant… to create a new plant. Building West Enter the plant name in the "File name" field, e.g. and click Save 35/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Page 36
Next > In the "Communication" dialog box, select "OZW775" as the central unit type. The following dialog box opens after your select the central communication unit type. 36/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant...
Page 37
Note: After a connection is opened: Symbol (= connect) becomes inactive and (= disconnect) becomes − active. The application changes to ACS Operating - [State – Connected] − 37/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Page 38
Devices outside the central communication unit line are displayed in the menu tree Note only if added manually to the device list; see Section 3.2.2 "Add devices". 38/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant...
Device address 150 Right-click (= central communication unit OZW 775) to open the list context menu and select Create device to start creating the device list. 39/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Right-click field "List of assigned devices" to open the context menu and select to start adding a device. Add devices… Dialog box "Insert devices" opens. Click Add device 40/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Page 41
Close dialog box ACS Operating – [Edit device Select Applications > Popcard… to open the [Popcard] and check if the device list contains the device(s). 41/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Close dialog box ACS Operating – [Edit device Select Applications > Popcard… to open the [Popcard] and check if the device was deleted from the device list. 42/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Plant > Edit device is selected. Workflow Select the symbol in the menu tree. Right-click to open the context menu and select Refresh device list to start refresh. 43/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
Select one or several devices from field "List of assigned devices". Right-click to open the context menu and select Refresh reference data points to start refreshing. 44/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products New plant 22.06.2012...
A plant with "central communication unit type OZW775" exists and the device list is up to date. Workflow Close all open applications and select Applications > Parameter settings… 46/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 47
- select to create a copy. Copy Right-click Device address 150 in the menu tree to open the context menu and select Paste to insert a copy. 47/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 48
"Parameter set properties" dialog box. Enter a new name for and con- Standard (1) firm by clicking The parameter set Standard is ready for parameterization. To do this, expand the menu tree. 48/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
"Popcard" or "Parameter Setting" from the Applications menu. The data points are displayed in the right window pane. Workflow Select Applications > Parameter settings… Fully expand the menu tree (continued on next page). 49/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
"Data point command" dialog Basic configuration box. • Select the desired value from the "Actual value" field, e.g. "Z02". • Click to enter the new value. 50/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Application [ Popcard ] "Commissioning mode = Off" Section 4.7 Application [ Popcard ] "Commissioning mode = Off" corresponds to normal mode in the central communication unit. 51/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775...
If one of the relays N.Q_ is connected to an FB "7-day time switch with control switch", relay N.Q_ in "Auto" position operates as per the time switch program, otherwise as per the control switch position "Off" or "On". 52/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 53
(alarming). Remote operation and monitoring are possible via modem (dial-up) and, at the same time, via Ethernet (Internet/intranet) to one (or several) web browsers. 53/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775...
Page 54
Cat-5 to connect to the Ethernet (Ethernet category 5 cable). The CE+ and CE- connection terminals labeled "KNX" are for the KNX bus. See data sheet N3127 for more information on the KNX bus. 54/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
1 and fault relay 2) output N.Q_. Max. 6 switching points (3 On, 3 Off) can be set per day for each time switch. 55/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775...
Page 56
Setting value N.X_ or N.D_ connects input 1…5 – of FB "Operating hours" to the terminal input to Default val: Setting val: ---, N.X1…N.X8 which the operation status contact is connected. N.D1…N.D8 56/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 57
• State "0" => messages are not inhibited. • State "1" => All messages are suppressed; i.e. they are not generated and, as a result, cannot be sent after message inhibition is cancelled. 57/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
/ standard time changeover. Mains frequency Setting value for mains frequency if DP "Time – synchronization = Mains frequency". Default val: 50 Hz Setting val: 50, 60 Hz 58/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 59
(LAN) and if it corresponds to the address structure. Range for IP addresses for private networks: 192.168.0.0 to 192.168.255.255. 59/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 60
IP address of the central communication unit entered as web server. DNS server 2 You must define DNS server 2 only in redundant – Default val: (Blank) systems. Setting val: Network admin. 60/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 61
The e-mail address is displayed in the "From" Setting val: Address, max. 20 alphanum. characters field of each e-mail. Internet Provider 61/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 62
Note: You must allow for display of the Network Connections symbol on the PC/laptop; see Help on network connections symbol in taskbar. This symbol provides direct access to the web server OZW775 rather than the IP address. 62/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 63
1 min This time ensures that the central communication unit can be called by modem between 2 connections (e.g. from an external operator station). 63/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 64
Select the telephone service provider and modem depending on the message receiver. If you use a GSM modem, make sure the SIM card allows for data communication and is not protected by a PIN code. 64/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 65
Default value. Example: Receiver type = E-mail. Interface = Ethernet (Default if receiver type = E-mail). Transmission protocol = SMTP (Default if receiver type = E-mail). 65/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 66
The default value (blank) means no default phone number ex works. Characters allowed: 0…9, /, -, w, W, =, @, !, &, <, space and comma ' , ' 66/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775...
Page 67
Default val: (Blank) Setting val: Max. 20 characters provider for certain services. The service number is also referred to as target number. 67/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Select the telephone service provider and modem depending on the message receiver. If you use a GSM modem, make sure the SIM card allows for data communication and is not protected by a PIN code. 68/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 69
– The measured value of the sensor can be Default val: Setting val: -3.0…3.0 K readjusted by +/- 3 Kelvin at DP "Correction". Resolution 0.1 K 69/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 70
ACS and messages. [Time switch 1…4] See the following table for setting value effect – inversion relay "No, Yes". Default val: Setting val: No, Yes 70/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 72
Fault input 1…20 Name (text) with max. 20 alphanumeric – characters. The name is displayed as Default val: (Blank) Setting val: Name information text in ACS and messages. 72/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 73
When 2 fault inputs "x" (from FB "Faults") are configured to fault input N.X_, an analog signal (e.g. temperature) can be monitored for "Limit value high" and "Limit value low" and normal value range between the values. 73/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 74
Accordingly, "Fault relay 1" or "Fault relay 2" are Default val: Fault system (acoustic) controlled only for "System" faults. Setting val relay 1 and 2: Fault local (visual) Fault local (acoustic) Fault system (acoustic) 74/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Resolution 00:10 screenshot below). If switching times were entered for a particular day, that day (screenshot, Tuesday) can be copied to other days with the same profile. 75/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775...
Each receiver offers a yearly calendar to enter holidays and special days. Messages are sent on days not listed in the calendar as holidays or special days. See example on the next page. 76/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775...
Page 77
• Holidays are displayed in red in the calendar; see 16.09.2005 (18:00); 26.09.2005 (07:00). • Special days are displayed in green, see 01.11.2005 (00:00); 01.11.2005 (23:59). • Special day 31.12.2005 is entered in the calendar, but has not yet been confirmed with 77/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Select the data points you want to download. parameter set Right-click to open the context menu and select Download 78/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Page 79
(better, the values) in the central communication unit (see below, transmission or download progress). Check if was successful. The "Transmission result" column Download parameter set must show OK. 79/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
Plant > Edit device Select the row with symbol in the right window pane and right-click to open the context menu. data points Select to start refreshing. Refresh reference 80/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
No, Yes checking inputs N.X1…N.X8 and N.D1…N.D8 as well as the outputs for Time switch 1…4 and Fault relay 1…2. See also Section 5.2 on "Wiring test". 81/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
(firmware) V2.02 or higher. Hardware version The data point is read-only. – Default val: 1.00 Setting val: Read-only 84/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
(clock time) and the current date. Default val: Monday, 1 January 2005 00:00 See Section 5.4.1 on "Time of day and date". Setting val: Date / Time 85/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Parameterize OZW775 22.06.2012...
After you complete the wiring and communication tests, you must reset the reference mode = Off data point to "Commissioning mode = Off" prior to starting normal mode. 87/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
Wiring test After you complete the wiring and communication tests, you must reset the reference active = No data point to "Wiring test active = No". 88/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
(see below with Meter 8 as an example). Requirements: • Reference data point "Wiring test active = No" • Reference data point "Commissioning mode = Off" 89/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
Time switch 1 and Time switch 3). Important note After you complete the wiring and communication tests, you must reset the reference data point to "Wiring test active" = No. 90/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
If the message receiver could not be reached, "System report sent = No" is displayed briefly, followed by "---". In this case, check the connection to the message receiver via the settings for the selected interface. 91/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
The interval does not change if a fault occurs that requires reporting between two sending attempts. The interval refers to the message receivers and not the fault status message. 92/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
However, all 4 message receivers can send within 8 minutes. "Current repetition interval" applies for unsent messages until the message receiver can send its message. 93/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
No dial tone, problem with local telephone cable. Possible causes: Wrong cable between modem and telephone connection, connection between modem and telephone connection interrupted, no telephone connection. 7 BUSY Phone number busy. 94/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
• Double-click the corresponding data point "Time switch 1…4" to open the dialog box, select operation selector position "Auto"/ "Off"/"On" and click to enter the values. 95/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
"Operating hours 1". • Double-click data point "Operating hours" to open the dialog box, set the required value and click to enter the value. 96/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
Note Note that the parameterized value "Message cycle = 7" first is written to data point "Next report" and overwritten only by the value setting (example 5). 97/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
2. Urgent "Local" faults 3. Not urgent "Local" faults Important note After commissioning, the red LED "Local" on the central communication unit must not be lit. 98/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
KNX network, under Faults "System". Important note After commissioning, the red LED "System" on the central communication unit must not be lit. 99/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
• Double-click data point "Delete history" to open the dialog box, select "Yes" and click to enter the value. Note Delete the history after commissioning or before you begin normal operation. 100/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps...
… • Click to open the dialog box and export or save the parameter set under a Export to meaningful file name. 101/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
Page 102
Blank page 102/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Further commissioning steps 22.06.2012...
The following sections use the term "web server" or "web server OZW775" rather than "central communication unit OZW775 as web server". In general, "web server" in this document always stands for "central communication unit OZW775 as web server". 103/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
You need a crossed Ethernet cable to connect the web server OZW775 to a PC/laptop. Straight cable You need a straight Ethernet cable to connect the web server OZW775 to a router, switch or hub. 104/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
Some Internet Service Providers block port 80. As a result, alternative ports open at the ISP must be found. Ports that are not 80 must be indicated in the URL. Example for port 5000 => 192.168.251.1:5000 105/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
Can you reach the web server? • Ping the web server from the PC/laptop on the same network (same network containing the web server OZW775): ping <IP address for web server>. 106/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
Page 107
• Clarify firewall issues with the network administrator and ISP (briefly deactivate the firewall as needed and check the connection). See next page for Steps 6 and 7. 107/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
Page 108
Step 7 If Steps 1 to 6 do not lead to success: • Contact the network administrator or support DSL provider, support router manufacturer, ISP. 108/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
(outbound), and as the SMTP transmission protocol is used for sending data via Ethernet (SMTP: Simple Mail Transfer Protocol). ISP stands for Internet Service Provider, as used in this document. 109/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
Internet. "Authentication mail server = Yes" checks unsecured, unencrypted information in the data points "User name" and "Password" from the mail server for each e-mail traffic. 110/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
<Domain DNS server> − nslookup <IP address DNS server> or nslookup <Domain DNS server> − See next page for Steps 2 to 6. 111/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
Page 112
Step 6 If Steps 1 to 5 do not lead to success: • Contact the network administrator or support DSL provider, support router manufacturer, ISP. 112/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
(= DSL router), DNS server). Note Sending fault messages and system reports via USB to PC/laptops with "ACS Alarm" is possible already from ACS CD V5.02. 113/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
Valid "All" or "Only urgent". Setting if not default: Default val: ……………………………………………………………….. Setting val: All, Only urgent faults * ACS alarm via Ethernet from ACS CD V5.10 114/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet 22.06.2012...
Check communication after you configure the data points and set up ACS Alarm on the PC/laptop. Send a test system report to a message receiver. If the test is successful, data point "System report sent" confirms with "Yes". 115/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
Page 116
Is the Windows firewall or any other firewall activated on the PC/laptop when "ACS Alarm" is installed? • If yes, deactivate the firewall for this application. For further diagnostics steps, refer to section 6.2.3. 116/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Communication via Ethernet...
Extended command language for modems: Attention+ Global System for Mobile communication Integrated Services Digital Networks ISDN Short Message Service Simple Mail Transfer Protocol SMTP Telocator Alphanumeric Protocol Universal Computer Protocol 118/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
An e-mail account to send e-mails is requested from the ISP. Web server OZW775 does not support SSL (Secure Sockets Layer) or HTTPS (Hyper Text Transfer Protocol Secure), i.e. e-mails cannot be sent secured and encrypted. 119/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
7.2.2 Configure DSL router and Internet connection Configure the DSL router as per the given topology to connect to the Internet. Siemens router Siemens Gigaset SX763 router is used for our example. See Section 7.2.8 for Gigaset SX763 information on this router.
Page 121
Setting value Attack Detection: Medium Network Address Activate NAT to ensure that the web server OZW775 can be reached via the Internet. Translation (NAT) Setting value NAT: 121/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 122
OZW775 Name to identify device. Note The configured firewall services are activated automatically for "Local IP address". Router SX763 does not need any other firewall settings. 122/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
The IP address can be entered automatically via DSL connection. If not possible, enter the IP address manually. The current address is displayed in the DSL router status message (see screenshot below). IP address in DSL router status message 123/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 124
The subnet mask 255.255.255.0. masks the first three bytes with "255.255.255" and only the fourth byte at ".0" can assume the values 0…255; however, note that the IP addresses cannot use 192.168.1.0 and 192.168.1.255. 124/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
• DNS server 1: 195.186.1.1 • DNS server 2: (blank) • UPnP localization: Note You do not need to address DNS server 2 (used only in redundant systems). 125/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 126
Protocol for encryption of data transmissions on the Internet. "Authentication mail server = Yes" checks unsecured, unencrypted information in the data points "User name" and "Password" from the mail server for each email traffic. 126/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix...
IP address. Request the domain names from the network administrator if you also want to access Note the web servers OZW775 via domain names. 127/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix...
Page 128
Request the following from the network administrator: • Company-internal e-mail account • Address mail server • Port number mail server • E-mail address sender • Authentication mail server • User name • Password 128/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
• E-mail address sender: silvan.zerla@siemens.com • Authentication mail server: No • User name: (Blank "Authentication mail server = No") • Password: (Blank "Authentication mail server = No") 129/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 130
After configuration, you can reach web servers OZW775 on the corporate network. Web server 1…x http://10.11.11.150 http://10.12.12.150 static IP addresses http://10.xy.xy.xy Web server 1…x http://agency1.siemens.com http://agency2.siemens.com domain names http://agencyx.siemens.com 130/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
7.2.8 Siemens router We recommend the following router from Siemens to connect to an internal network with DSL connection: Gigaset SX763 WLAN dsl This router supports all requirements for trouble-free operation of web server OZW775. Price: Ca. CHF 145 http://gigaset.siemens.com...
DNS server. Port forwarding (NAT, PAT) is also configured in the router. In addition, service "DynDNS", which automatically is updated after a change of the DynDNS server, is activated in the router. 133/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 134
The IP protocol determines the order and network connection used to send data packages (routing). The transmission control protocol TCP reassembles the data packages in the right order at the recipient. 134/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix...
Page 135
Use the network adapter (hardware) to connect a network device to a local network LAN. Connection can be wired or wireless. For example, an Ethernet network card for PC/laptop or Ethernet card OZZ7E5 in web server OZW775 is a wired network adapter. 135/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 136
A router forwards data packages from a local network LAN to a higher network while selecting the fastest route. A router allows for connecting different networks with different network topologies. For example, the router connects a local network to the Internet. 136/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix...
Page 137
Family of protocols used as the basis for the Internet. TCP/IP is the basis for many Internet services such as "www". E-mails are sent unsecured, i.e. without TSL, a protocol to encrypt data transmissions TSL (Transport Layer on the Internet. Security) 137/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 138
In addition, they automatically provider own services or use services of other devices on the network. URL (Uniform Resource A URL is the information source, e.g. http://www.siemens.com. The URL is a unique Locator) web address that identifies a resource via the network protocol used (e.g. http) and the location of the resource on the network.
= interface Making the configuration: = from here = to there From uppercase to uppercase letter = Time switch From lowercase to lowercase letter = Fault 139/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Device failure (bus) is a "System fault" sent by the central communication unit. This is why it is listed in this table. The central communication unit only detects all other "System faults" and indicates them depending on parameterization. 144/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Phone number receiver..........76 Fault status message delay ........73 Port number ACS alarm ........66, 114 Fault text ..............82 Port number mail server ........61, 110 Fax protocol .............. 63 145/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...
Page 146
Value low ..............70 Text for: Logic 0...........69, 70 Text for: Logic 1...........69, 70 Wiring test active ............81 Text for: No fault............74 Text for: Service done ..........72 146/148 Siemens Building Technologies Commissioning instructions OZW775 V2.01 CE1C5663en HVAC Products Appendix 22.06.2012...