4: Notification Appliance Circuits; 5: Ili-Mb-E3 And Ili95-Mb-E3 Outputs; 6: Ili-Mb-E3 And Ili95-Mb-E3 Specifications - Honeywell Gamewell-FCI E3 Series Installation & Operation Manual

Expandable emergency evacuation system
Hide thumbs Also See for Gamewell-FCI E3 Series:
Table of Contents

Advertisement

ILI-MB-E3 and ILI95-MB-E3 Connections
3.1.4 Notification Appliance Circuits
The ILI-MB-E3 or ILI95-MB-E3 provides two (2), 24
VDC Class A, Style Z or Class B, Style Y notification
appliance circuits. See Figure 3.1.4.1 for wiring
information. See the Compatibility Addendum,
P/N: 9000-0427, for a list of approved compatible
devices.
Wiring Instructions:
NAC 1 – Style Y
NAC 2 – Style Y
NAC 1 – Style Z
NAC 2 – Style Z
(Polarity markings indicate the polarity of the circuit in
alarm condition). Use UL Listed End of Line Resistor
EOL-N (33K), P/N 4700-0484 for Class B, Style Y
wiring.
Circuit Ratings:
24 VDC (Nom.) FWR
Max. alarm load: - 2.0 amp/circuit
Ground fault test impedance: Zero ohms
Supervised - Power-limited
18 AWG minimum
MDL3 Series Synchronization Modules must be
connected. Special application: See Compatibility
Addendum, P/N 9000-0427 for a list of Gamewell-FCI
approved, UL Listed notification appliances.
3.1.5 ILI-MB-E3 and ILI95-MB-E3 Outputs
The ILI-MB-E3 or ILI95-MB-E3 provides output for a Local Energy City Master Box, reversing
polarity output for leased line connection, or Releasing Service.
Ratings
Nominal Voltage
Supervisory Current:
Alarm Current:
Line Resistance
Trip Coil Resistance
3.1.6 ILI-MB-E3 and ILI95-MB-E3 Specifications
The following lists the electrical specifications for the ILI-MB-E3 and ILI95-MB-E3.
Specifications
Operating Voltage:
Operating Current:
Alarm Current:
Operating Temperature:
Relative Humidity:
Supervised
Power-limited
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
TB2-6 out, TB2-8 return
Master Box (NPL)
Polarity Reversal (PL)
24 VDC
24 VDC
.0018 amp
.012 amp
.510 amp (max.)
.012 amp
35 Ohms (max.)
14.5 Ohms (max.)
Table 3.1.5.1 ILI-MB-E3 and ILI95-MB-E3 Outputs
ILI-MB-E3
24 VDC (from PM-9/PM-9G
power supply)
0.081 amp
0.150 amp
32° to 120° F (0° to 49° C)
0 to 93% non-condensing at 90° F
(32° C)
E3 Series System Connections
EOL
-
+
-
+
B (-)
ILI-MB-E3/
ILI95-MB-E3
A (-)
DOTTED LINES INDICATE CLASS A,
STYLE Z WIRING. REMOVE EOL
FOR CLASS A, STYLE Z
OPERATION
Figure 3.1.4.1 Notification Appliance
Releasing Service
24 VDC
.0005 amp
.700 amp
2 Ohms (max.)
ILI95-MB-E3
24 VDC (from PM-9/PM-9G
power supply)
0.050 amp
0.091 amp
0 to 93% non-condensing at 90° F
(32° C)
B (+)
A (+)
Circuits