E3 Series System Connections

3.5 Intelligent Loop Interface XP95-Slave Board Connections

3.5.1 Signaling Line Circuits
The ILI95-S-E3 provides two (2),24 VDC Class A,
Style 6, 7 or Class B, Style 4 signaling line circuits.
See Figure 3.5.1.1 for wiring information. Style 7
wiring requires the use of an M500X Isolator Module,
(ILI-S-E3), or XP95-LI Line Isolator or
XP95-LIB Line Isolator Base (ILI95-S-E3) on both
sides of a device.
Wiring Instructions
SLC 1 Style 4
SLC 1 Style 6
SLC 2 Style 4
SLC-2 Style 6
(Polarity markings indicate the polarity that should be
maintained throughout the circuit. Polarity connected
to the circuit must be observed on all devices).
Circuit Ratings
24 VDC (nominal)
FWR
Current:
Ground fault test
impedance:
Wiring:
Power-limited
110
Intelligent Loop Interface XP95-Slave Board Connections
TB7-3 (-), TB7-4 ( + )
TB4-3 (-), TB4-4 (+)
TB7-1 return, TB7-2 return
TB7-3 out, TB7-4 out
TB4-1 return, TB4-2 return
TB4-3 out, TB4-4 out
0.051 amp Max (supervisory)
0.136 amp max. (alarm)
0.100 amp max. Steady State
(short circuit)
40 Ohms max. line impedance
0.5 µf max. line capacitance
Zero ohms
18 AWG minimum,
twisted-pair, unshielded
Supervised
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
INPUT/CO NTRO L
M O DULE
SM O K E/HEAT
SENSO R
NCM -1
ILI95-S-E3
B (-)
A (-)
DO TTED LINES INDICATE CLASS A ,
STYLE 6 W IRING .
Figure 3.5.1.1 Signaling Line Circuits
B (+)
A (+)