3: Anu-48 Wiring Connections - Honeywell Gamewell-FCI E3 Series Installation & Operation Manual

Expandable emergency evacuation system
Hide thumbs Also See for Gamewell-FCI E3 Series:
Table of Contents

Advertisement

E3 Series System Connections
3.12.3 ANU-48 Wiring Connections
Table 3.12.3.1 lists the field wiring connections for the ANU-48.
NOTE: For ASM-16 or ANU-48 wiring details, Section 3.9.3 ASM-16 or ANU-48 Wiring
Connections (Table 3.9.3.1 and Figure 3.9.4.1).
Designation
TB1-1
TB1-2
TB1-3
TB1-4
TB5-1
TB5-2
TB5-3
TB5-4
TB5-5
TB5-6
TB5-7
TB5-8
TB5-9
TB5-10
TB5-11
TB5-12
TB6-1 to -8
TB7-1 to -8
TB8-1 to -8
TB9-1 to -8
TB10-1 to -8
TB11-1 to -8
TB12-1 to -8
TB13-1
TB13-2
J1
J2
J3
JMP1
JMP2
JMP3
JMP4
JMP5
* 5 V @ 0.5 ma. Max
NOTE 1: LED outputs are power-limited and unsupervised (the ANU-48 must be located within 20
feet of the annunciator). Cable connections are color coded to the LEDs.
NOTE 2: When more than four (4) ANU-48's are required, use an external regulated, power-limited,
power supply Listed for use with fire protection signaling units.
NOTE 3: Programmable SPST switches maintained or momentary (must be unsupervised and
located within 20 feet). Cable connections are color coded to programmable N/O switches.
160
Description
COMM A
Twisted-unshielded pair (To ANU-48 TB1-1 COMM A)
COMM B
Twisted-unshielded pair (To ANU-48 TB1-2 COMM B)
+24
Single Discrete Wire (To ANU-48 TB1-3 +24)
GND
Single Discrete Wire (To ANU-48 TB1-4 GND)
SW1
*SPST - maintained or momentary
SW2
*SPST - maintained or momentary
SW3
*SPST - maintained or momentary
SW4
*SPST - maintained or momentary
SW5
*SPST - maintained or momentary
SW6
*SPST - maintained or momentary
SW7
*SPST - maintained or momentary
SW8
*SPST - maintained or momentary
Common for SW1, SW2
Common for SW3, SW4
Common for SW5, SW6
Common for SW7, SW8
LEDs 1 to 8
Negative outputs to remote LEDs
LEDs 9 to 17
Negative outputs to remote LEDs
LEDs 18 to 26
Negative outputs to remote LEDs
LEDs 27 to 33
Negative outputs to remote LEDs
LEDs 34 to 42
Negative outputs to remote LEDs
LEDs 43 to 48
Negative outputs to remote LEDs
LED1-48+
Positive common output for remote LEDs
EXT PWR +
+ From external power supply (max. 24 VDC)
EXT PWR -
- From external power supply
RS-485 input connection to ANU-48
RS-485 connection to next ANU-48
Program
Factory use
Factory use
IN when using internal power
IN when using external power
Factory use
Factory use
Table 3.12.3.1 ANU-48 Wiring Connections
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
ANU-48 Remote LED Driver Connections
Comments

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents