System Overview

1.5 Specifications

1.5.1 Power Supply (PM-9/PM-9G)
The following are the specifications for the PM-9 and PM-9G power supply sub-assemblies.
Specifications
Input Voltage:
Input Current:
Output Voltage:
Output Current:
Output Current:
Output Current
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:
Supervised
Non Power-Limited
NOTE 1: Continuous standby loads in excess of .560 Amps up to 5 Amps may require a
Generator Backup or load shedding during an AC power failure. See Section 3.15 (Standby
Battery Calculations Chart) in this Manual.
NOTE 2: Continuous standby loads in excess of .560 Amps up to 4 Amps may require a
Generator Backup or load shedding during an AC power failure. See Section 3.15 (Standby
Battery Calculations Chart) in this Manual.
1.5.2 Signaling Line Circuits (ILI-E3 or ILI95-E3 Series)
Two (2), Class "A", Style 6, 7,* or Class "B" Style 4 circuits
ILI-S-E3)
Capacity of 126 sensors/modules per circuit (ILI95-MB-E3 or ILI95-S-E3)
*Style 7 operation requires System Sensor, M500X Isolator Module (ILI-MB-E3 or ILI-S-E3) or
XP95-LI Line Isolator and XP95-LIB Line Isolator Base (ILI95-MB-E3 or ILI95-S-E3).
Refer to the Compatibility Addendum to Gamewell-FCI Manuals, P/N 9000-0427, Section 1 for a
list of UL Listed, compatible sensors/modules.
16
PM-9
120 VAC, 60 Hz
4.6 amps max. @ 120 VAC 60 Hz 2.4 amps max.
24 VDC FWR
9 amperes Alarm max. continuous 9 amperes Alarm max. continuous
5 amperes max. continuous
Standby (when the PM-9 is used
with the ILI-E3 or the ILI95-E3
Series) (See Note 1)
4 amperes max. continuous
Standby (when the PM-9 is used
with any AM-50 Series amplifier)
(See Note 2)
0 to 93%, non-condensing at 90° F
(32° C)
Table 1.5.1.1 PM-9/PM-9G Specifications
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Specifications
PM-9G
240 VAC @ 50/60 Hz
24 VDC FWR
5 amperes max. continuous Standby
(when the PM-9G is used with the
ILI-E3 or the ILI95-E3 Series)
(See Note 1)
4 amperes max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier) (See Note 2)
0 to 93%, non-condensing at 90° F
(32° C)