6: Dact-E3 Wiring Connections - Honeywell Gamewell-FCI E3 Series Installation & Operation Manual

Expandable emergency evacuation system
Hide thumbs Also See for Gamewell-FCI E3 Series:
Table of Contents

Advertisement

E3 Series System Connections
3.10.6 DACT-E3 Wiring Connections
Table 3.10.6.1 lists the DACT-E3 wiring connections.
Designation
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
150
Digital Alarm Communicator Transmitter (DACT-E3) Connections
Description
COM A IN
COM A from ILI-MB-E3/ILI95-MB-E3/ANX
COM B IN
COM B from ILI-MB-E3/ILI95-MB-E3/ANX
COM A OUT
COM A OUT to other devices
COM B OUT
COM B OUT to other devices
+24 V IN
+ 24 VDC from PM-9/PM-9G TB4-1, TB4-3 or TB4-5
GND
GND from PM-9/PM-9G TB4-2, TB4-4 or TB4-6
T1 Tip
Line 1 Tip IN from street Non power-limited
T1 Ring
Line 1 Ring IN from street Non power-limited
P1 Tip
Line 1 Tip OUT to phone Non power-limited
P1 Ring
Line 1 Ring OUT to phone Non power-limited
T2 Tip
Line 2 Tip IN from street Non power-limited
T2 Ring
Line 2 Ring IN from street Non power-limited
P2 Tip
Line 2 Tip OUT to phone Non power-limited
P2 Ring
Line 2 Ring OUT to phone Non power-limited
Table 3.10.6.1 DACT-E3 Wiring Connections
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10