Summary Of Audible Notification - Honeywell VISTA-128FBPT User Manual

Commercial fire and burglary partitioned security systems with scheduling
Hide thumbs Also See for VISTA-128FBPT:
Table of Contents

Advertisement

Summary of Audible Notification

(Alpha Display Keypads)
SOUND
CAUSE
LOUD,
FIRE ALARM
INTERRUPTED*
Keypad & External
LOUD,
BURGLARY/AUDIBLE EMERGENCY
CONTINUOUS*
ALARM
Keypad & External
ONE SHORT BEEP
a. SYSTEM DISARM
(not repeated)
b. SYSTEM ARMING ATTEMPT
Keypad only
WITH AN OPEN ZONE.
c. BYPASS VERIFY
ONE SHORT BEEP
SYSTEM IS IN TEST MODE
(once every 15
sec.) Keypad only
TWO SHORT BEEPS
SYSTEM IS ABOUT TO
(once every 5 sec.)
AUTOMATICALLY EXIT TEST
Keypad only
MODE
ONE BEEP
LOW BATTERY AT A TRANSMITTER
(every 60 sec.)
Keypad only
TWO SHORT BEEPS
ARM AWAY OR MAXIMUM
Keypad only
THREE SHORT
a. ARM STAY OR INSTANT
BEEPS
b. ZONE OPENED WHILE SYSTEM
Keypad only
IS IN CHIME MODE.
RAPID BEEPING
a. TROUBLE
Keypad only
b. AC POWER LOSS ALERT**
c. MEMORY OF ALARM
SLOW BEEPING
a. ENTRY DELAY WARNING
Keypad only
b. EXIT DELAY WARNING
(if programmed)
*
If bell is used as Notification Appliance, fire alarm is pulsed ring; burglary/audible emergency is steady ring.
** Loss of system battery power is not indicated or annunciated by the keypad (warnings are for loss of AC power only).
– 68 –
National Security Systems (800)457-1999
http://nationalsecuritysystems.com
DISPLAY
FIRE is displayed; descriptor of zone in alarm is
displayed.
ALARM is displayed; descriptor of zone in alarm is
also displayed.
a. DISARMED/READY TO ARM is displayed.
b. The number and descriptor of the open protection
zone is displayed.
c. Numbers and descriptors of the bypassed
protection zones are displayed (One beep is heard
for each zone displayed). Subsequently, the
following is displayed: DISARMED BYPASS Ready
to Arm
Opened Zone identifications will appear.
Opened Zone identifications will appear.
LO BAT displayed with description of transmitter.
ARMED AWAY or ARMED MAXIMUM is displayed.
Red ARMED indicator is lit.
a. ARMED STAY ZONE BYPASSED or ARMED
INSTANT ZONE BYPASSED is displayed. Red
ARMED indicator is lit.
b. CHIME displayed, descriptor of open protection
zone will be displayed if the [Q] key is pressed.
a. CHECK displayed. Descriptor of troubled
protection zone is displayed.
b. AC LOSS displayed (may alternate with other
displays that may be present).
c. FIRE or ALARM is displayed; descriptor of zone in
alarm is displayed.
a. DISARM SYSTEM OR ALARM WILL OCCUR is
displayed. Exceeding the delay time without
disarming causes alarm.
b. ARMED AWAY or ARMED MAXIMUM is displayed
along with You May Exit Now

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-250fbpt

Table of Contents