Connecting Unshielded Lines; Maintenance - Bosch Rexroth IndraControl L10 Project Planning Manual

Table of Contents

Advertisement

Project Planning Manual | Rexroth IndraControl L10

Connecting Unshielded Lines

8.3

Maintenance

Fig.8-6:
Connecting lines to the tension spring connectors
Wire the connectors as required according to the application.
Proceed as follows to wire the connectors:
Strip the line to a length of 8 mm. Wiring is provided without connector
sleeves. However, connector sleeves may be used, if desired. In this case,
the connector sleeves must be properly crimped.
Put a screwdriver into the actuation slot of the appropriate terminal point
(figure 8-6, A) as far as necessary to be able to insert the core into the
opening of the spring. Insert the core (figure 8-6, B). Pull the screwdriver
out of the opening. This fixes the core. We recommend to label both the
cores and the terminal points after completed installation.
Include the following measures in the maintenance schedule:
At least once a year, check all plug and terminal connections for proper
tightness and damage. Verify that lines and cables are not broken or
squeezed. Replace damaged parts immediately.
Electric Drives
| Bosch Rexroth AG
and Controls
Installation and Maintenance
43/54

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents