Display And Operating Components; General Information; Reset Button And Status Led - Bosch Rexroth IndraControl L10 Project Planning Manual

Table of Contents

Advertisement

Project Planning Manual | Rexroth IndraControl L10
6

Display and Operating Components

6.1

General Information

6.2

Reset Button and Status LED

Reset button
The
web-based
"IndraControl
IndraControl L10 for the display and the operation. The control can be accessed
with a web browser via an Ethernet interface. The IP address is set to
192.168.1.10 when shipped. Further information under /1/.
The reset button and the status LED are located on the front of the
IndraControl L10.
The Reset button and the multicolor LED are located on the left side of the
device front.
Fig.6-1:
Recessed reset button and status LED
Pressing the reset button will abort processing of a running pro‐
gram.
The reset button can only be pressed using a tool, for instance with the tip of a
pencil.
Three different actions can be activated using the Reset button:
1.
Short pressing of the reset button during the operation resets the complete
assembly and forces a restart the without a switch off of the supply vol‐
tages.
2.
Long pressing of the reset button during the operation resets the complete
assembly and forces a restart without a switch off of the supply voltages.
Additionally, the IP address is reset to the delivery status (192.168.1.10).
Therefore, the reset button is to be pressed till the booting phase ends.
The period of the booting phase is indicated with an orange status light
emitting diode.
3.
If the reset button is pressed during the switch-on voltage of the power
supply, the existing boot project is deleted.