Used Standards - Bosch Rexroth IndraControl L10 Project Planning Manual

Table of Contents

Advertisement

16/54
Bosch Rexroth AG | Electric Drives
Technical Data
DANGER
4.4

Used Standards

and Controls
Air pressure
Mechanical strength
Degree of pollution
Fig.4-4:
Ambient conditions
The surrounding air must be free from acids, alkaline solutions,
corrosive agents, salts, metal vapors, and other electrically con‐
ductive contaminants in high concentrations.
The ambient air must be free from dust. Housings and installation
compartments must at least comply with degree of protection IP 54
according to DIN VDE 0470-1.
Danger of destruction by overheating
Ensure a surrounding air temperature of less than 55 °C.
The IndraControl L10 complies with the following standards:
Standard
DIN EN 60 204-1
DIN EN 61,131-2
DIN EN 60,529
DIN EN 50 178
Fig.4-5:
Used standards
The IndraControl L10 complies with the CE requirements!
Rexroth IndraControl L10 | Project Planning Manual
In operation
Up to 2700 m above MSL
according to DIN 60204
Max. vibration:
Frequency range:
10...150 Hz
Excursion: 0.003 in at
10..0.57 Hz
Acceleration: 1 g at
57...150 Hz
According to EN
60068-2-6
2
Meaning
Electrical equipment of machines
Programmable logic controllers
Requirements on the equipment and tests
Degrees of protection (incl. housings and installation
compartments)
Electronic equipment for use in power installations
Storage / Transport
Up to 3000 m above MSL
according to DIN 60204
Max. shock:
15 g according to EN 60
068-2-27, no disturbance of
the function
2