2.3.16.11.2 Edit Settings (If CB Fail Status is enabled)
GROUP 1
CB FAIL
CB Fail Status
Enabled
CB Fail Timer
0.10 S
CBF Reset
CB Open+ I<
P153/EN M/B
By using the (5) or (6) key, I< can be set. The setting range is from
0.05 to 3.2 In in steps of 0.01 In
By using the (5) or (6) key, IN< can be set. The setting range is from
0.05 to 3.2 In in steps of 0.01 In
Editable setting
By using the (5) or (6) key, Remove I> Start can be Enabled /
Disabled
Editable setting
By using the (5) or (6) key, Remove IN> Start can be Enabled /
Disabled
Password protected window for "GROUP 1'' setting i.e. SYSTEM
CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
Password protected window for CB FAIL i.e. CB Fail Status, CB Fail
Timer, CB Reset, I<, IN<, Remove I> Start and Remove IN> Start.
Editable setting
By using the (5) or (6) key, CB Fail Status is Enabled.
Editable setting
By using the (5) or (6) key, CB Fail Timer can be set. The setting
range is from 0 to 50s in steps of 0.01s.
By using the (5) or (6) key, CBF Reset can be set as CB Open + I<,
Prot Reset + I<, CB Open, I<