13 Technical Specifications
Dielectric voltage
1.2
withstand test
Insulation resistance
1.3
test
Creepage distances
1.4
and clearances
13-8
1) 2kV rms for 1 minute between all terminals connected together with case earth.
IEC 60255-27:2005
2) 2kV rms for 1 minute between independent circuits with case earth.
(incl. corrigendum 2007)
3) 1.5kV rms for 1 minute across open contacts of changeover output relays.
IEC 60255-27:2005
> 100 MΩ at 500V DC
(incl. corrigendum 2007)
Pollution degree
IEC 60255-27:2005
(incl. corrigendum 2007)
Overvoltage category : III
: 2
P50 Agile P153
P153/EN M/B