GE Agile P50 Series Technical Manual page 179

Compact feeder protection relay
Table of Contents

Advertisement

P50 Agile P153
Sr. No
4.
This time multiplier setting is used to adjust the operating time of the IEC / UK IDMT characteristic.
5.
This time multiplier setting is used to adjust the operating time of the IEEE / US IDMT curves.
6.
This setting determines the type of reset/release characteristics. IDMT applicable for IEEE curves only.
7.
This setting determines the reset/release time for IEEE IDMT characteristic
8.
This setting determines the reset/release time for Definite Time (DT) and all IDMT curve
9.
This setting determines the enabling/disabling of blocking first stage measured earth fault element due to presence of inrush current.
If IN1>1 Blocking and 2nd Harmonic settings are enabled, then (IN1>1) trip command will be blocked in case 2nd harmonics content in
any phase is above the 2ndHarm Thresh. and fundamental current is below I> lift 2H setting . (Set in SYSTEM CONFIG Menu.)
2.12.3.2
IN1>2 Function
Sr. No
1.
This setting determines the tripping characteristic for the second stage measured earth fault element.
2.
This setting determines the pick-up setting for second stage measured earth fault element.
3.
This setting determines the time-delay for the definite time setting if selected for second stage of measured earth fault element.
4.
This time multiplier setting is used to adjust the operating time of the IEC / UK IDMT characteristic.
5.
This time multiplier setting is used to adjust the operating time of the IEEE / US IDMT curves.
6.
This setting determines the type of reset/release characteristics. IDMT applicable for IEEE curves only.
7.
This setting determines the reset/release time for IEEE IDMT characteristic
8.
This setting determines the reset/release time for Definite Time (DT) and all IDMT curve
9.
This setting determines the enabling/disabling of blocking second stage measured earth fault element due to presence of inrush current.
If IN1>2 Blocking and 2nd Harmonic settings are enabled, then (IN1>2) trip command will be blocked in case 2nd harmonics content in
any phase is above the 2ndHarm Thresh. and fundamental current is below I> lift 2H setting . (Set in SYSTEM CONFIG Menu.)
2.12.3.3
IN1>3 Function
Sr. No
P153/EN M/B
Parameter
IN1>1 TMS
1.000
IN1>1 Time Dial
1.00
IN1>1 Reset Char
DT
IN1>1 RTMS
1.000
IN1>1 tRESET
1.00 S
IN1>1 2H Blocking
Disabled
Parameter
IN1>2 Function
IEC S Inverse
IN1>2 Current Set
1.00*In
IN1>2 Time Delay
1.00 S
IN1>2 TMS
1.000
IN1>2 Time Dial
1.00
IN1>2 Reset Char
DT
IN1>2 RTMS
1.000
IN1>2 tRESET
1.00 S
IN1>2 2H Blocking
Disabled
Parameter
7 Protection Parameter Settings
Default setting
Default setting
Default setting
Setting Range
0.025 to 1.2 step 0.005
0.01 to 100 step 0.01
DT/IDMT
0.025 to 1.2 step 0.005
0s to 100s step 0.01s
Enabled / Disabled
Setting Range
Disabled / DT / IEC S Inverse / S Inverse
(1.3Sec) / IEC V Inverse / IEC E Inverse / UK
LT Inverse / IEEE M Inverse / IEEE V Inverse
/ IEEE E Inverse / US Inverse / US ST
Inverse
If DT 0.05 to 35.00*In step 0.01*In
If IDMT then 0.05 to 4.00*In step 0.01*In
0s to 200s step 0.01s
0.025 to 1.2 step 0.005
0.01 to 100 step 0.01
DT/IDMT
0.025 to 1.2 step 0.005
0s to 100s step 0.01s
Enabled / Disabled
Setting Range
7-13