GE Agile P50 Series Technical Manual page 76

Compact feeder protection relay
Table of Contents

Advertisement

P50 Agile P153
I>1 Time Delay
01.00 S
I>1 Reset Char
DT
I>1 tRESET
1.00 S
I>1 2H Blocking
Disabled
Note: The settings of I>2 Function and I>3 Function should be done in a similar manner as I>1 Function.
2.3.16.4
Group1 –Negative Sequence Overcurrent Submenu
Edit Settings
2.3.16.4.1
GROUP 1
NEG SEQUENCE O/C
I2>1Function
Disabled
I2>2Function
Disabled
P153/EN M/B
(if I2>1 Function, I2>2 Function and I2>3 Function are disabled)
Editable setting
By using the (5) or (6) key, I>1 Time Delay can be set. The setting
range is from 0 to 100s in steps of 0.01s.
Read-only
I>1 Reset Char is fixed as DT (Definite Time).
Editable setting
By using the (5) or (6) key, I>1 tRESET can be set. The setting range
is from 0 to 100s in steps of 0.01s.
Editable setting
By using the (5) or (6) key, I>1 2H Blocking function can be Enabled
/ Disabled.
Password protected window for "GROUP 1'' setting:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
By using the (5) or (6) key, select the NEGATIVE SEQUENCE O/C
setting menu in Group 1.
Password protected window for NEGATIVE SEQUENCE O/C settings:
I2>1 Function, I2>2 Function and I2>3 Function can be set as Disabled /
DT / IEC S Inverse/ S Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/
UK LT Inverse /IEEE M Inverse/ IEEE V Inverse/ IEEE E Inverse /US
Inverse /US ST Inverse
Editable setting
By using the (5) or (6) key, I2>1 Function is Disabled.
Editable setting
By using the (5) or (6) key, I2>2 Function is Disabled.
5 Configuration
5-38