GE Agile P50 Series Technical Manual page 73

Compact feeder protection relay
Table of Contents

Advertisement

P50 Agile P153
2nd Harm Thresh
20%
I>lift 2H
10.00 A
2.3.16.3
Group1 –Overcurrent Submenu
Edit Settings
2.3.16.3.1
GROUP 1
OVERCURRENT
I>1Function
Disabled
I>2Function
Disabled
I>3Function
Disabled
Edit Settings
2.3.16.3.2
GROUP 1
OVERCURRENT
P153/EN M/B
(if I>1 Function, I>2 Function and I>3 Function are disabled)
(if I>1 Function is selected for IEC curve)
Editable setting
By using the (5) or (6) key, the desired 2ndHarm Thresh can be set.
The setting range is 5% to 70% in steps of 1%.
Editable setting
By using the (5) or (6) key, the desired I>lift 2H setting can be done.
The setting range is 4.00 to 32.00 In in steps of 0.01 In.
Password protected window for "GROUP 1'' settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
Password protected window for Overcurrent i.e. I>1 Function, I>2
Function and I>3 Function setting to Disabled / DT/ IEC S Inverse/ S
Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/ UK LT Inverse /IEEE M
Inverse/ IEEE V Inverse/ IEEE E Inverse /US Inverse /US ST Inverse
Editable setting
By using the (5) or (6) key, I>1Function can be Disabled
Editable setting
By using the (5) or (6) key, I>2Function can be Disabled
Editable setting
By using the (5) or (6) key, I>3Function can be Disabled
Password protected window for "GROUP 1'' setting:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
Password protected window for Overcurrent i.e. I>1 Function, I>2
Function and I>3 Function setting to Disabled / DT/ IEC S Inverse/ S
Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/ UK LT Inverse /IEEE M
Inverse/ IEEE V Inverse/ IEEE E Inverse /US Inverse /US ST Inverse
5 Configuration
5-35