P50 Agile P153
IN2>1 2HBlocking
Disabled
Edit Settings
2.3.16.7.4
GROUP 1
EARTH FAULT 2
Derived
IN2>1 Function
DT
IN2>1 Current Set
1.00 A
IN2>1 Time Delay
1.00 S
IN2>1 Reset Char
DT
IN2>1 tRESET
1.00 S
P153/EN M/B
(if IN2>1 Function is selected for DT)
Editable setting
By using the (5) or (6) key, IN2>1 2HBlocking function can be
Enabled / Disabled.
Password protected window for "GROUP 1'' settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
Password protected window for Earth Fault 2 (derived) i.e. IN2>1
Function, IN2>2 Function and IN2>3 Function which can be set as
Disabled / DT / IEC S Inverse/ S Inverse (1.3Sec)/ IEC V Inverse/ IEC E
Inverse/ UK LT Inverse /IEEE M Inverse/ IEEE V Inverse/ IEEE E
Inverse /US Inverse
Read-only
Description for Earth Fault 2
Editable setting
By using the (5) or (6) key, IN2>1Function is set as DT.
Editable setting
By using the (5) or (6) key, IN2>1 Current Setting can be set. The
setting range is from 0.1 to 35.0 In in steps of 0.01In.
Note: For I>3 Function. the setting range is from 1.0 to 35.0 In in steps of
0.01In
Editable setting
By using the (5) or (6) key, IN2>1 Time Delay can be set. The setting
range is from 0 to 200s in steps of 0.01s.
Read-only
IN2>1 Reset Char is fixed as DT (Definite Time).
Editable setting
By using the (5) or (6) key, IN2>1 tRESET can be set. The setting
range is from 0 to 100s in steps of 0.01s.