OPERATION
Resetting the Totalizer Count
● Repeat step 1 above, but specifying register #4117 instead (Length = 1).
● Repeat step 2 above (no need to change serial configuration if already configured).
● Double click on the register number (see pointer in the figure below). A pop-up Write Register window displays. Enter the defined hex
value, 0xABCD, in the window's value field, and then click Update.
Figure 48 – ModScan32 Connected to Modbus Device with Register 4117 on Display (Totalizer Reset)
Starting/Stopping the Totalizer Count
● Repeat step 1 above, but specifying register #4118 instead (Length = 1).
● Repeat step 2 above (no need to change serial configuration if already configured).
● Double click on the register number (see pointer in the figure below). A pop-up Write Register window displays. Enter the defined
value (1 = start or 0 = stop) in the window's value field, and then click Update.
Figure 49 – ModScan32 Connected to Modbus Device with Register 4118 on Display (Totalizer Start/Stop)
80
MT100 Multipoint Flow Meter
Fluid Components International LLC