OPERATION

Flow Damping

The flow meter has a flow damping setting that is used to smooth out the flow signal output for applications in which process conditions are
erratic. Use the configurator software to adjust the flow damping setting (Advanced Setup/User Parameters) as required for your
application. Refer to the MT100 Configuration Software manual 06EN003461 for details.
As shown in Figure 33 below, an increase in flow damping value results in an output that is increasingly resistant to change (amplitude
variations). Compare the chart's blue curve (value = 0.25 for 0% flow damping) with the chart's black curve (value = 5.00 for 95% flow
damping). The black curve shows signal excursions that are much more constrained relative to the blue curve.
The minimum value that can be entered is 0.25 (0% flow damping). It is possible to enter a number greater than 5.0 (95% flow damping).
The practical limit, however, is 5.0 since 100% flow damping will never be attained regardless of the entered value.
Caution:
65.000
64.800
64.600
64.400
64.200
64.000
63.800
63.600
0
36
High flow damping values results in reduced flow response. Make sure that alarm conditions are not affected when
using the flow damping feature.
50
Data Logger Samples (Every 250 mS or 240/Minute)
Figure 33 – Chart: Flow Output Over Time with Various Flow Damping Values
100
150
MT100 Multipoint Flow Meter
Damping = 0.25
Damping = 1.00
Damping = 3.00
Damping = 5.00
200
250
Fluid Components International LLC
300
C01406-1-1