MT100 Multipoint Flow Meter
F
Fieldbus/PROFIBUS (Option)
OUNDATION
The optional MT100 F
accepts 26-14 AWG (0.14 mm
Fieldbus/PROFIBUS device/network as shown in Figure 26 below. Use the provided cable clamp to secure the wires to the board. Note
that devices are connected in parallel (star fashion). For Fieldbus, a terminator (1 µF capacitor and 100 Ω resistor in series) is used on
farthest ends of the trunk (i.e., at each end of the segment cable). For details on PROFIBUS operation refer to the MT100 PROFIBUS PA
manual 06EN003474. For details on F
F
/PROFIBUS A
IELDBUS
As shown in
Figure 20
(JP18), #NV_ERASE (JP19), and #HW_LOCK (JP20) test signals. This provides a means to activate a "simulate mode" for Fieldbus
conformance testing and for add-on card testing/diagnostics. Enable a particular signal by installing a 0.100" jumper shunt over the
appropriate header pins. For normal use none of these jumpers are installed.
Relay Outputs
The MT100 relay interface is provided by the J11 Phoenix connector terminals. The relay connector accepts 28-16 AWG (0.14 mm
) wire. Using J11 connect the SPDT relay outputs to the appropriate external circuits as shown in Table 4 below. Relay Contact
mm
2
Rating: 6 A (resistive load).
Relay 1 (K1) Terminal
Relay 2 (K2) Terminal
Note: 1. J11 terminals 4 and 5 are unused/no connection.
Fluid Components International LLC
Fieldbus/PROFIBUS interface is provided by the J26 Phoenix connector terminals. The connector
OUNDATION
-1.5 mm
) wire (refer to
2
2
OUNDATION
-O
C
D
DD
N
ARD
IAGNOSTICS
on page 23, a bank of 0.100" jumpers control the optional Fieldbus/PROFIBUS add-on card's #SIM_ENABLE
FB_A
MT100
Fieldbus/
PROFIBUS
Interface (J26)
FB_B
Figure 26 – Fieldbus/PROFIBUS Wiring
Table 4 – J11 Relay Contacts Pinout
J11-3 (COM1)
(Pin Label)
J11-8 (COM2)
(Pin Label)
Table
2, page
23
for wire size vs. length info). Connect the MT100 to a
Fieldbus operation refer to the MT100 F
/T
J
EST
UMPERS
Wire Pair
T
Signals
Terminator
Terminator
Common
Normally Open
J11-2 (NO1)
J11-7 (NO2)
Fieldbus manual 06EN003472.
OUNDATION
Add'l
Field
Device
Field
T
Device
C01407-1-1
Normally Closed
J11-1 (NC1)
J11-6 (NC2)
INSTALLATION
-1.5
2
29