PV500 series solar pumping inverters
Function
code
Delay time of
P15.24
wake-up at weak
Initial reference
P15.25
voltage display
Min. voltage
reference during
P15.26
max. power
Name
Detailed illustration of parameters
Note: If the bus voltage is lower than the
undervoltage point or the PV voltage is
lower than 70V, it will report the weak
light alarm without any delay time.
If P15.32=0, the system will switch to the
power frequency input when the light is
weak.
0.0~3600.0s
Delay time of wake-up at weak light
If the weak light alarm is reported, after
the delay time of wake-up, the alarm will
be cleared and it will run again.
light
When P15.32=0, if the PV voltage is
higher than P15.34, after the delay time,
it will switch to PV input mode.
0.0~2000.0V
0.00~1.00
This function code is used to set the
minimum voltage reference during
maximum power tracking. Min. voltage
reference during max. power tracking =
Solar cell panel open-circuit voltage *
P15.26. Solar cell panel open-circuit
tracking
voltage = P15.25+ P15.28
Track the maximum power in the range
of Min. voltage reference~P15.27.
P15.27 must be greater than Min.
voltage reference. The less the
-53-
Function parameters
Default Modify
300.0s
0
0.70