PV500 series solar pumping inverters
Function
code
P15.10
PI switching point
P15.11
Water level control
Name
Detailed illustration of parameters
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
0.0~6553.5Vdc
If the absolute value of bus voltage
minus the reference value is bigger than
P15.10, it will switch to P15.08 and
P15.09; otherwise it is P15.06 and
P15.07.
0: Digital input of the water-level control
1: AI1(the water-level signal is input
through AI1, not supported currently)
2: AI2 (the water-level signal is input
through AI2)
3: AI3 (the water-level signal is input
through AI3)
If the function code is 0, the water-level
signal is controlled by the digital input.
See 43 and 44 functions of S terminals in
group P05 for detailed information. If the
full-water signal is valid, the system will
report the alarm (A-tF) and sleep after
the time of P15.14. During the alarm, the
full-water signal is invalid and the system
will clear the alarm after the time of
P15.15. If the empty-water signal is valid,
the system will report the alarm (A-tL)
and sleep after the time of P15.16.