HBD PV500-0007M1 User Manual page 15

Solar pump inverter
Table of Contents

Advertisement

PV500 series solar pumping inverters
Environment
Running
environment
condition
Pollution
Altitude
Vibration
Installation
direction
Note:
PV500 series inverters should be installed in a clean and ventilated environment
according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The inverter may be installed on the wall or in a cabinet.
The inverter needs be installed in the vertical position. Check the installation site according to
the requirements below. See Appendix D Dimension drawings for frame details.
3.1.3 Installation manner
(1) The inverters ≤ 2.2kW support wall mounting and rail mounting.
a) Wall mounting
The installation site of the inverter should:
Keep away from the electromagnetic radiation source;
Keep away from contaminative air, such as corrosive gas, oil mist and
flammable gas;
Ensure foreign objects, such as metal power, dust, oil, water cannot
enter into the inverter(do not install the inverter on the flammable
materials such as wood);
Keep away from direct sunlight,
environment.
Pollution degree 2
Below 1000m
If the altitude is above 1000m, please derate 1% for every additional
100m.
2
≤ 5.8m/s
(0.6g)
The inverter should be installed on an upright position to ensure
sufficient cooling effect.
Conditions
oil mist, steam and
b) Rail mounting
-13-
Installation guidelines
vibration

Hide quick links:

Advertisement

Table of Contents
loading