PV500 series solar pumping inverters
Function
code
Lower frequency
P15.05
of PI output
P15.06
P15.07
P15.08
P15.09
Name
Detailed illustration of parameters
target frequency, and 100.0%
corresponds to P00.03.
After PI adjustment, the target frequency
cannot exceed the upper limit.
0.0%~P15.04 (100.0% corresponds to
P00.03)
P15.05 is used to limit the Min. value of
target frequency, and 100.0%
corresponds to P00.03.
After PI adjustment, the target frequency
cannot be less than the lower limit.
0.00~100.00
Proportion coefficient 1 of the target
KP1
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
0.00~100.00
Integral coefficient 1 of the target
KI1
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
0.00~100.00
Proportion coefficient 2 of the target
KP2
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
0.00~100.00
KI2
Integral coefficient 2 of the target
-48-
Function parameters
Default Modify
20.0%
5.00
5.00
35.00
35.00