PV500 series solar pumping inverters
Function
code
P00.18
restore parameter
P01 Group Start-up and stop control
P01.08
Stop mode
Name
Detailed illustration of parameters
It is recommended to use rotation
autotuning when high control accuracy is
needed.
2: Static autotuning
It is suitable in the cases when the motor
cannot de-couple form the load. The auto
running for the motor parameter will
impact the control accuracy.
3: Static autotuning 2 (No autotuning for
non-load current and mutual inductance)
0: No operation
1: Restore the default value
2: Clear fault records
Note:
The function code will restore to 0 after
Function
finishing the operation of the selected
function code.
Restoring to the default value will cancel
the user password. Use this function with
caution.
0: Decelerate to stop. After the stop
command becomes valid, the inverter
decelerates to reduce the output
frequency during the set time. When the
frequency decreases to 0Hz, the inverter
stops.
1: Coast to stop. After the stop command
-30-
Function parameters
Default Modify
0
0