Vent Restrictor Installation

1. Determine the venting configuration.
2. Go to venting arrangements section (in the manual) to determine if
a vent restrictor setting is required. (If required, proceed to Step 3).
3. Loosen the two screws that secure the top heat deflector and remove
top heat deflector (diagram 1).
4. Align the vent restrictor plate (found in the manual package) to the required
vent restrictor position as per the Diagrams shown.
5. Once the vent restrictor plate is in the required position, secure with 2 -
1/4" x 1/2" screws. Ensure all screws are tight, but do not over tighten.
Set 0
Fully Open

Venting Introduction

The G800C uses the "balanced flue" technology Co-Axial system. The
Set 1
inner liner vents products of combustion to the outside while the outer liner
2" Open
draws outside combustion air into the combustion chamber thereby elimi-
nating the need to use heated room air for combustion and losing warm
room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside
of the building, and never be attached to a chimney serving a separate solid
fuel or gas burning appliance. Each direct vent gas appliance must use it's
own separate vent system. Common vent systems are prohibited.
Set 2
1-3/4" Open
Diagram 1: Top heat deflector
Diagram 2: Vent restrictor located on top exhaust assembly
Grandview® G800C Gas Fireplace
installation
|