Test - Ip Communication With Controller; Figure 52: Eco Mode Status - Gamatronic B60US-IB Installation Manual

Three phase modular ups for the 208v grid
Table of Contents

Advertisement

Next verify the system is in ECO mode and the load is supported via the static switch.
6. From the System Menu go to Status.
The Status screen appears:
Notice that the Status screen message indicates UPS ON and ECO mode.
The system will run on ECO mode until either there is a variant in the grid power
supply or manually transferred back to inverter.

Test - IP Communication with Controller

3.4.6.
This test is designed to verify that the System Controller is properly configured for remote
monitoring. Verifying communication and that the Web server built into the System Controller is
functioning properly.
You may skip this step if you do not intend to use remote monitoring of the UPS at
this time.
UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0

Figure 52: ECO Mode Status

65