Connecting The Ups To The Electrical Panel; Figure 11: Terminal Connections - Gamatronic B60US-IB Installation Manual

Three phase modular ups for the 208v grid
Table of Contents

Advertisement

Access to the main terminals on the B60US-IB can be obtained by simply opening
the back door of the UPS.
To the electrical panel to which the UPS is connected, affix a sign or label with the
following message:
WARNING: There is a UPS attached to this electrical panel. To avoid
following
warning:
electric shock, DO NOT DISCONNECT THE UPS's NEUTRAL LINE WHEN THE
UPS IS OPERATING.

Connecting the UPS to the electrical panel

3.3.4.4.
When connecting the electrical panel to The Gamatronic UPS, a torque of 10 to 20 Nm is
recommended on the UPS terminal side. The lug size needed to fit a 3/8" or metric M10 screw
size.
Suitably rated circuit breakers must be installed between the UPS and the electrical panel.
UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0

Figure 11: Terminal connections

31