Continuing First Time UPS configuration

3.3.6.2.
To continue the first time startup process:
1. If you are using lithium-ion batteries, contact Gamatronic support for configuration
instructions and check the values in the Setup > Battery parameters against the
information in the battery manufacturer's data sheet. Verify that the parameter values
are appropriate for the batteries you have chosen.
2. Turn off the bypass and rectifier input circuit breaker.
3. Insert a single power module and connect the right and left flat cables (as shown in
Figure 27 above).
4. If the bypass and input are bridged, slide out the static switch (See Figure 28 above) at
least 5 inches.
5. Turn on the rectifier input circuit breaker, wait for the power module to be fully
UPS for 208 Vac Grid, Installation Guide, doc. rel. 3.0

Figure 27: Flat cables

Figure 28: Static Switch

46