This installation guide is for product #101SW463-1. AMATRONIC HREE HASE ODULAR 208V FOR THE GRID B60US-IB INSTALLATION GUIDE Revision 3.0, January 2020 (Doc. 2MUM-B60I)
Page 2
Remember to register your product at: http://www.gamatronic.com/product-warranty in order to activate your warranty. UPS for 208 Vac Grid, Installation Guide, doc. rel. 3.0...
Page 3
Most of the electrical abbreviations in this document are according to IEEE 280 Standard Letter Symbols for Quantities Used in Electrical Science and Electrical Engineering. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 6
Common vs. Decentralized battery ........................79 6.1.2.2. 6.2......................79 NSTRUCTIONS FOR PARALLEL CONFIGURATION Maintenance bypass for parallel systems .................... 87 6.2.1. MAINTENANCE BYPASS MODE PROCEDURE ....................88 7.1............................. 89 IRCUIT BREAKER LAYOUT 7.2............89 RANSFERRING THE TO MAINTENANCE BYPASS MODE FROM NORMAL MODE 7.3.
Page 8
Figure 48: Changing the auxiliary contact to normally closed ............. 62 Figure 49: ECO Mode.......................... 63 Figure 50: Enable ECO mode ......................64 Figure 51: Turning on ECO mode ....................... 64 Figure 52: ECO Mode Status ......................65 Figure 53: Web View ........................... 66 Figure 54: Location of Connector Groups 1 and 2 on the front of the UPS.
Verify that their indicators are not red. A red indicator is a sign of rough handling (ShockWatch) or tip-over (TiltWatch). Notify the carrier and Gamatronic Support immediately if rough handling of the UPS is suspected or if any damage is found or suspected.
- OR - Figure 2: ShockWatch and TiltWatch devices These devices indicate if the package was subject to shock or tip-over. 4. Using a forklift, move the shipping crate close to the place in which the UPS will be installed. 5.
Be careful to avoid scratching the finish of the Modular UPS. 10. Lift the UPS from the shipping pallet and move it to the location where it will be installed. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
2. Safety Precautions The UPS system is designed for a wide range of environments. Nevertheless, the modular UPS should be handled with care, according to the following guidelines. 2.1. Do’s Read this manual and the User Guide carefully before starting installation and operation of the ...
Page 13
The battery cabinet contains a series of batteries that provides high voltage and energy in the UPS body even when the UPS is not connected to the ac input. Take appropriate precautions during installation, inspection and servicing. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
2.2. Don’ts Do not open the cover of the UPS or the battery cabinets under any circumstances. All UPS panels and doors should be closed. Do not insert any objects through the ventilation holes. Do not put objects on the UPS. ...
Up to 3 power modules, each provides 20 kVA / 18 KW Static switch module System controller Up to 3 internal battery banks Maximum output capacity of the UPS is 60 kVA/54 kW. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 5: Major components of the UPS system Figure 6: Main terminals viewed from the UPS rear UPS for 208 Vac Grid, Installation Guide, doc. rel. 3.0...
3.1. Important Installation Information The Gamatronic UPS must be connected in a “4-wire + Ground” configuration (i.e., 3 phases + Neutral + Ground). The voltage displayed on the status screen is the Phase-to-Neutral voltage. The Neutral line MUST be connected to the UPS on the input and output stages of the UPS. The UPS will support phase-to-phase loads and phase-to-Neutral loads.
Reference column) for detailed information about each checklist item. The detailed explanation of each section can be found in section 3 .3 and Section 0 . When the checklist is complete, e-mail it to your vendor and to Gamatronic at Support@gamatronic.com.
Page 19
Before wiring the system, verify that all possible voltage sources are disconnected, and the following circuit breakers are in the “OFF” position: Rectifier ac input, bypass ac input, ac output and all battery cabinets. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 20
Verify that wire sizes for ac input, bypass ac Verify that all ac phase, input, ac output and battery cabinet(s) meet neutral, dc pole and local code for maximum current values. midpoint wire sizes and Figure 9 circuit breakers meet local Figure 10 code for maximum Verify that input and output circuit breakers...
Page 21
10V, charge the battery set that voltage = 200V (± 8 %). has the lowest voltage, until the differences across SW3 and SW4 are less than 10 V. 19.4 Turn off all battery CBs UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 22
Note: the static switch will supply output power from the bypass. Initial Configuration Type the password you receive from the Gama app, Gamatronic support or at: Password accepted http://license.gamatronic.com/ Note the Hardware ID number Enter the Ah value of the battery set.
Page 23
11. Turn on the system (main>operation>on/off>system on) 12. The system will transfer to bypass, then once all inverters are fully operational the system will transfer the output to the inverter (i.e., Normal Mode) UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 24
√ Check DC voltage Turn on the battery circuit breakers and wait for the dc relays to connect the rectifer to the battery. If the battery voltage is low verify that the battery is charging and wait until the battery reaches its floating voltage.
Page 25
Testing and Setup 46. Verify that the system is running on normal mode at full capcity. 47. Verify that the batteries are connected and at floating volatge ±216 Vdc. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 26
Confirm that there are no system alarms. Battery test: preform a battey test main>operation> battery test. The batteries are required to hold the inverter DC voltage and pass until the end of the 5 minutes. Self-Load test: During system commissioning, the charger, inverter and bypass of the UPS module shall be tested at full load without the need for an external load bank.
Perform the following procedures before connecting any external cables to the UPS. To perform the physical site preparation procedure: 1. Ensure that the ambient temperature in the immediate vicinity of the UPS complies with system requirements: UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 28
Minimum/maximum operating temperatures: +14°F / +104 °F (–10 °C / +40 °C). 2. Recommended operating temperature: Between +59°F and +77 °F (+15°C and +25 °C). 3. Verify that there is no water condensation or dampness at the installation site. 4.
20 cm free space between the UPS and the other equipment. The object here is to avoid subjecting the UPS to additional heat and to protect the UPS from stray electronic signals. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
2. Verify that circuit breakers on the electrical panel that supplies the UPS are compliant with local and national codes and Gamatronic system specifications. 3. Verify that the input and output power cable connections, ground, and neutral lines comply with local and national codes and are appropriate for the circuit breakers protecting them.
7. FAST FUSES (SEMICONDUCTOR FUSES) must be used between the battery and the Gamatronic UPS. For example, the Ferraz Shawmut A70QS fuse (F1, F2, F3 and F4 in Figure 16. Be sure to verify proper polarity. 8. For initial startup to take place, the battery must be connected to the UPS and must be available.
The Neutral Line 3.3.4.2. When the UPS is operating, a neutral line must be connected at all times and must not be disconnected at any time. Caution: If at any time the neutral line becomes disconnected, there will be no input or output reference voltage because the input neutral line and the output neutral line are physically linked together.
Connecting the UPS to the electrical panel 3.3.4.4. When connecting the electrical panel to The Gamatronic UPS, a torque of 10 to 20 Nm is recommended on the UPS terminal side. The lug size needed to fit a 3/8" or metric M10 screw size.
A suitably rated fuse must be installed on the rectifier ac input line and bypass input line. Refer to Figure 9 or Figure 10 for system connections and to Table 2 for circuit breaker recommendations. See Chapter 5 for an overview of circuit breaker selectivity. Warning: Connection of The UPS to the electrical panel must be performed only by a licensed electrician experienced with similar systems.
If one or more of the battery strings are not used, remove the trays and store them externally to the unit. All battery terminal connection torque values must be in accordance with the battery manufacturer specifications. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 16: Link the four batteries on each side of the tray Bus bar links with insulated covers are provided to link 4 batteries on either side on the tray together. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 17: For safe disconnection of the batteries There are 2 wires with cable plugs on one end and Anderson plugs on the other to connect the 4 and 5 battery on each tray. They allow for a safe disconnect of every 48V. Be sure to use the terminal insulators.
The UPS supports the use of standard lead-acid batteries as well as lithium- ion batteries. If you plan on using lithium-ion batteries, consult with Gamatronic Support to insure that the battery setup parameter values are appropriate for the batteries you will be using.
6. If you are using lithium-ion batteries, contact Gamatronic support for configuration instructions. Figure 20: Connecting a Single Battery Set UPS KVA UPS KW DC CURRENT Table 3: Battery current ratings for semiconductor fuses and circuit breakers 7. The fuses between the battery cabinets and The UPS (F1, F2, F3, and F4 in Figure 20) must be FAST FUSES (SEMICONDUCTOR FUSES);...
Figure 21: Connecting multiple battery sets, using CBs Figure 21 shows how two battery sets can be connected to the UPS. This example includes two circuit breakers (DC SW #1 and #2), one for each battery pole. Fuses F5, F6 and of DC SW #1 and #2 (for each battery set) in Figure 21 have the same values as those specified in Figure 20.
A series of screens are displayed on the control panel to enable you to perform initial UPS system configuration. Initial Configuration 3.3.6. After initial system configuration is performed for the first time, the initial configuration Wizard will not appear again. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
System Startup Wizard 3.3.6.1. When the UPS is initially started up, a series of configuration screens are presented on the LCD display panel. You will be prompted to provide the UPS with basic system configuration information in order to enable initial operation of the UPS. To perform first time UPS configuration: 1.
The Password screen appears: Figure 23: Initial configuration wizard: password entry 3. Type the Technician password you received from Gamatronic in the Password text input field and press OK. Without a password you cannot continue. The Battery Capacity screen appears:...
If you are not sure of your batteries’ Ah capacity, check one of the batteries in the battery cabinet(s). The Ah rating is usually indicated on the battery's exterior. The Ah rating of a single battery is the same as for the entire cabinet. When using multiple battery banks the Ah value of each battery bank must be added (i.e.
The Finish screen appears: Figure 26: Finish configuration wizard 6. Press Finish. The System Menu wizard exits. 7. Continue the first time installation process (Section 3 .3.6.2 below). UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
3.3.6.2. To continue the first time startup process: 1. If you are using lithium-ion batteries, contact Gamatronic support for configuration instructions and check the values in the Setup > Battery parameters against the information in the battery manufacturer’s data sheet. Verify that the parameter values are appropriate for the batteries you have chosen.
The Modules Off screen appears: Figure 29: Modules Off Screen 7. Select the power module icon. The selected power module is highlighted with a blue border. 8. Select Complete Shutdown. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
The selected power module is shutdown. 9. Insert the next power module 3/4 of the way in and attach the 2 flat cables then, slide it in fully. 10. Turn on the power module (Main > Operation > Turn On/Off > Modules on). The Modules on screen appears: Figure 30: Modules 11.
27. In the System Menu screen, if the Alarm symbol (a red circle with a white “x” in the middle) is displayed, press the Alarm symbol to display any potential problems. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
For additional information about responding to Alarm indications, refer to the Troubleshooting Guide. Figure 33: The "alarms" icon indicates alarm conditions Next perform a brief battery test to verify that The UPS is ready and it is able to operate in battery mode when needed.
32. Transfer the unit to bypass. (Operation > Transfer load > Transfer to bypass) The Transfer load to bypass appears: Figure 36: Confirm Transfer Load to Bypass 33. Select OK. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
34. You can now connect a load device to the ac output circuit breaker and then turn ON the ac output circuit breakers on the electrical panel. 35. If working with operating loads turn off the maintenance bypass circuit breaker to move the load to the UPS.
> Save settings. The Save User Settings screen appears: Figure 39: Confirm Save User Settings 42. Confirm OK. The User Settings are saved. The system is now supporting the load. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Assigning IP Address to the UPS 3.3.6.3. This procedure assigns an IP address to the UPS. Assigning an IP address allows you, the user, to remotely monitor The UPS over an IP network. If you do not intend on remotely monitoring the UPS, you can skip this step. If you decide to later implement remote monitoring, you can perform this process at that time.
DNS address and a secondary DNS address. 48. Type the addresses (including digits and dots that make up the address) using the virtual keyboard of the LCD panel in the appropriate text input fields. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
To select an address field on the screen, tap the field with your finger. Depending on the particular model of screen on your system, dragging your finger lightly across the field from right to left may yield best results. 49. When you have completed entering all of the addresses, select Confirm. The addresses you entered are saved to the UPS system controller.
8. Wait until the system starts in PQ mode. 9. Navigate to the UPS ON PQ Output screen by selecting Main > Status. The UPS On PQ Output status screen appears: UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 44: PQ Mode 10. Verify that the rectifier input current level has gone up and the Static switch is bridged to the inverter (See Figure 44). 11. Repeat steps 6 through 10 to adjust PQ power, by increasing the load level in 10% increments.
The system is returned to VF mode. The system is back in full operation and is ready to be used as a UPS. Test: Under load 3.4.2. This test is designed for standard load bank testing to verify the operation of UPS under load. To perform the test under load: 1.
2. From the Generator drop down menu choose dry contact 2 and select Confirm. Now that it is enabled the battery charging current will be limited when the contact opens or closes depending on controller setting configuration. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
To change the System Controller setting from the default N.O. (normally open) to N.C. (normally closed): 1. From the System Menu go to input dry contact settings by choosing Setup > Dry contacts > Input dry contacts. The Input Dry Contacts screen appears: Figure 48: Changing the auxiliary contact to normally closed 2.
Figure 49: ECO Mode 2. Select ECO mode. A Gamatronic key is required for ECO mode. If ECO mode has not been enabled via a Gamatronic key, the system will prompt you for the key before the feature may be accessed.
The ECO mode screen appears: Figure 50: Enable ECO mode 3. The system controller must enable ECO mode. In the ECO mode screen, select the Enabled checkbox and then select Confirm. 4. Navigate to Operation (Main > Operation). The following screen appears: Figure 51: Turning on ECO mode 5.
Verifying communication and that the Web server built into the System Controller is functioning properly. You may skip this step if you do not intend to use remote monitoring of the UPS at this time. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
The following procedure is given in general terms; the specifics will vary depending on the operating system of the computer you are using. To test IP Communication with the Controller: 1. Use an RJ45-to-RJ45 straight or crossed cable to attach a PC or laptop or other external computer to the Ethernet (RJ45) port on the UPS’s system controller.
Figure 54: Location of Connector Groups 1 and 2 on the front of the UPS. The location of connector groups 1 and 2 is shown in Figure 54 and close-up views of the connectors are shown further on in the text where relevant. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 55: Close-up of Connector Group 1 Table 5: Key to 1 Figure 55: Close-up of Connector Group 1 ESCRIPTION P23 Load-on-bypass dry contact, N.O. Forced Bypass contacts. N.O. When these contacts are closed, the UPS immediately goes into bypass mode. These contacts are intended to be used in conjunction with the Maintenance Bypass function.
Digital output #3 Do NOT remove P2 or P13 Digital output #4 Digital output #5 Digital output #6 Digital output #7 Digital output #8 RS485 Modbus A RS485 Modbus B UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Page 74
RS485 Parallel A RS485 Parallel B Temp. sensor #1 A Temp. sensor #1 B Temp. sensor #2 A Temp. sensor #2 B Digital input #1 Common Digital input #2 (Optional: Generator mode) Common Digital input #3 Surge protector fault Common Digital input #4 (Optional: Maintenance bypass) Common...
Page 75
Negative Battery Current -12 V Digital output #2 Common Digital output #1 Remote panel PWR Remote panel DAT Remote panel CLK Remote panel Gnd RS232 TX RS232 RX RS232 Gnd UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
4.1. Input and output dry contacts The UPS has input and output dry contacts. The input dry contacts enable the UPS’s computer to monitor the state (open or closed) of a relay external to the UPS, and to generate an alarm if the state of the external relay changes. The output dry contacts enable the UPS to trigger an external circuit in response to a system alarm.
12AWG or of a cross-section area 2.5 mm is recommended. Figure 58: LVD wiring diagram For additional information about configuring the LVD function, refer to the UPS User Guide. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
5. Circuit Breaker Selectivity When discussing power distribution, “selectivity " (also referred to as “discrimination”), it is the selection and arrangement of circuit breakers such that in the event of a short circuit or overload in the line, the circuit breaker closest to the short will be tripped and the upstream circuit breakers remain unaffected.
Page 79
If local electrical codes are more stringent than the recommendations presented above, the local code takes priority. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
6. Parallel Operation 6.1. Theory When two or more UPS units are deployed in parallel, they are connected according to the decentralized Static Switch method (see below). Special technical solutions and control algorithms are implemented to synchronize all units in the system to prevent circulation of energy between them and to isolate a faulty unit from the common power bus.
"ring configuration" arrangement. This is accomplished by the use of Gamatronic-provided cables with D25 connectors on each end. Parallel communication keeps the parallel units synchronized with each other and is used to pass commands and status information between units.
Figure 61: Parallel comm. connections (see Table 7) Figure 62: Location of the parallel comm. connections at inside rear of the system Connections for the two parallel communication cables when two or more UPS’s are being operated in parallel configuration. All parallel communication cables (the 25-pin cables) must be housed in appropriate conduits.
Common vs. Decentralized battery 6.1.2.2. Gamatronic UPS systems running in parallel can be setup in one of two ways to batteries. 1. Common battery. Is a single battery connection that is shared between all the UPS systems that are running in parallel.
UPSs, and the bypass input cables must be at least 10 meters in length. 3. Connect the UPSs in a ring configuration using two parallel kit communication cables on each UPS. For parallel systems with common battery, contact Gamatronic support for special cable. UPS for 208 Vac Grid, Installation Guide, doc. rel. 3.0...
5. Turn on one of the systems. This system will become the “master” system. Wait until the startup procedure is complete. When the startup procedure completes you will be presented with the main System Menu screen as below: UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 65: System Menu main screen The screen should display UPS ON, Normal mode message, and there should be no alarms present. If there are active alarms, resolve any problems before continuing. 6. Put the UPS in multisystem mode (System Menu > Setup > System > Multisystem mode).
If the difference in output voltage is greater than 2 % for any phase, navigate to the System Menu > Status screen, tap the Modules icon, and then tap the Output tab at the bottom of the page. The following screen appears: UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Figure 68: Ac output voltage display for a single module 11. You will see the ac output voltage display, per module. By tapping on each of the module icons on the left side of the screen you can see which modules have an output voltage that is more than 2 %.
The rating of circuit breaker CB12 in the connection schematics must be appropriate for the number of parallel UPSs. Table 8: Rating of CB12 (for maintenance bypass option) UMBER OF ECOMMENDED RATING FOR CB12 (A PARALLEL UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
7. Maintenance Bypass Mode Procedure In maintenance bypass mode, the UPS does not to supply power to the load and UPS is isolated from the mains power. This enables a technician, after turning off ALL the input, output and battery circuit breakers, to work safely on the UPS. The technician can perform full maintenance procedures, load testing and even replace the unit without any interruption of power to the load.
Transferring the UPS to maintenance bypass mode from normal mode In normal operation, the UPS's ac circuit breakers are positioned as shown in Table 9 (see Figure 71 for CB locations). UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Table 9: Normal mode operating position of the circuit breakers Battery box input Rectifier ac input Bypass ac input UPS AC output Maintenance bypass (on battery box) (CB 2) (CB 3) (CB 5) (CB 6) To put the system in maintenance bypass mode: 1.
The UPS On – Bypass mode screen appears: Figure 74: UPS ON - Bypass mode Notice the UPS ON Bypass mode message on the screen. 7. Verify that the load is being supported by the bypass. UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
Then, operate the UPS's ac circuit breakers as follows: 1. Switch ON the MAINTENANCE BYPASS circuit breaker. 2. Switch OFF the AC OUTPUT circuit breaker. 3. Switch OFF the RECTIFIER AC INPUT circuit breaker. 4. Switch OFF the BYPASS AC INPUT circuit breaker. 5.
Table 12: Position of the CBs in normal mode Battery box input Rectifier ac input Bypass ac input UPS AC output Maintenance bypass (on battery box) (CB 2) (CB 3) (CB 5) (CB 6) UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0...
8. Using the UPS with a Generator At many sites a generator is used as a reserve source for feeding the UPS during mains power failure. 8.1. The Automatic Transfer Switch (ATS) In such cases, the switching between the two sources (the mains and the generator) is performed by an Automatic Transfer Switch (ATS).
9. Service and Repairs IMPORTANT NOTICES 1. Any company whose technicians have been trained by Gamatronic and has received proper authorization and certification has Gamatronic’s permission to apply modifications to our products in North America. Modifications could entail adding or removing modules as well as performing service or maintenance.