IRST
7.1

Cable connections.

To connect the required cables to the UPS:
1.
Ensure that the lines coming into the UPS are equipped with circuit breakers of the
following capacity:
UPS output:
Ac input:
The following table gives the recommended cable sizes that must be used when
connecting the UPS. The table states the cable's cross-sectional area in mm
If local codes are stricter, they have priority.
Ac output
Gnd, N, L1, L2, L3
2
6 mm
User Guide: MEGA V2 SA25, Release 1.5
Gamatronic Electronic Industries Ltd.
TIME SETUP
Only an authorized electrician may wire the UPS power connections.
Do not attempt to wire any of the power connections on your own.
3x40 A Class C
3x40 A Class C

Table 5: Recommended cable diameters.

Ac input
Gnd, N, L1, L2, L3
2
6 mm
Battery input
2
6 mm
(Use the battery cable supplied
by Gamatronic.)
2
.
31