SECTION 2 - INSTALLATION
TABLE 2 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR FOR FLOODED EVAPORATOR UNITS -
LBS (KGS)
SHELLS
A-A
C-B
C-C
C-C
D-D
D-D
E-E
E-E
E-I
F-F
G-E
H-F
J-J
L-L
K-K
K-K
K-O
M-M
M-M
M-U
N-N
N-N
P-P
Q-Q
Q-Q
R-R
R-R
S-S
S-V
X-T
X-X
W-W
Z-Y
Z-Z
NOTE: Refrigerant charge quantity and weights will vary based on tube count, configuration, and chiller performance. Use for reference only.
Refer to YORKworks Performance Page or chiller nameplate for actual charge requirement.
42
COMPRESSOR
Q3
13,100 (5,942)
Q4
18,023 (8,175)
Q3, Q4
14,920 (6,768)
Q5
15,330 (6,954)
Q3, Q4
17,215 (7,809)
Q5
17,625 (7,995)
Q3, Q4
17,950 (8,142)
Q5,Q6,Q7,P7
18,360 (8,328)
Q7
23,567 (10,690)
Q5,Q6,Q7,P7
18,720 (8,491)
P8
20,300 (9,208)
P8,P9
23,100 (10,478)
P8,P9
24,000 (10,886)
P8,P9
27,400 (12,429)
H9
28,530 (12,941)
K1
31,100 (14,107)
H9
34,483 (15,641)
H9
34,200(15,513)
K1,K2
38,300 (17,373)
K2
45,178 (20,493)
K1,K2
28,530 (18,549)
K3
48,000 (21,773)
K1,K2
41,500 (18,824)
K1,K2
45,300 (20,548)
K3
46,000 (20,865)
K3
52,800 (23,950)
K4
53,000 (24,041)
K4
59,000 (26,672)
K4
60,100 (27,261)
K4
59,200 (26,853)
K4
66,000 (29,937)
K7
79,500 (36,061)
K7
95,300 (43,196)
K7
80,500 (36,515)
SHIPPING
OPERATING WEIGHT
WEIGHT
LBS (KGS)
LBS (KGS)
15,000 (6,804)
22,323 (10,126)
17,940 (8,138)
18,350 (8,324)
21,100 (9,571)
21,510 (9,757)
22,160 (10,052)
22,570 (10,238)
29,384 (13,328)
23,880 (10,832)
24,200 (10,977)
28,000 (12,701)
29,100 (13,200)
33,900 (15,377)
36,000 (16,329)
36,200 (16,420)
44,776 (20,310)
43,600 (19,777)
47,100 (21,364)
58,017 (26,316)
50,800 (23,043)
54,100 (24,540)
51,900 (23,542)
56,800 (25,764)
60,200 (27,307)
70,300 (31,888)
70,600 (32,034)
76,300 (34,609)
81,300 (36,877)
80,000 (36,288)
87,000 (39,463)
104,000 (47,174)
123,015 (55,799)
105,000 (47,628)
FORM 160.75-N1
ISSUE DATE: 4/30/2014
ESTIMATE
REFRIGERANT
CHARGE LBS (KGS)
810 (367)
1,525 (692)
1,240 (562)
1,240 (562)
1,680 (762)
1,680 (762)
1,710 (776)
1,710 (776)
1,805 (819)
2,175 (987)
1,990 (903)
2,610 (1,184)
2,550 (1,157)
3,165 (1,436)
2,925 (1,327)
3,248 (1,473)
3,260 (1,479)
3,665 (1,662)
3,665 (1,662)
3,540 (1,606)
4,225 (1,916)
4,225 (1,916)
3,855 (1,749)
4,255 (1,930)
4,255 (1,930)
4,660 (2,114)
4,785 (2,170)
4,940 (2,241)
5,500 (2,495)
5,125 (2,325)
5,625 (2,551)
6,900 (3,130)
6,555 (2,973)
6,275 (2,846)