Installing The Uc Open Into The I-Vu® Application - Carrier UC Open Installation And Startup Manual

Table of Contents

Advertisement

Installing the UC Open
Wiring communication
1
Turn off the UC Open's power.
2
Wire the TruVu™ ET Display's RS485 connector to the <ALCProduct>'s Rnet port, Gnd to Gnd, + to Rnet +, - to
Rnet - using 2-conductor 22 AWG wire with a maximum distance of 500 feet (152 meters).
3
Turn on the UC Open's power.
For complete TruVu™ ET Display installation instructions, see the TruVu™ ET Display Installation and Start-up
Guide.
Installing the UC Open into the i-Vu® application
You must complete the following procedures to successfully install your UC Open into an i-Vu® Control System.
Use the Help in the referenced software for detailed descriptions of these procedures.
EquipmentBuilder or Snap
1
Use EquipmentBuilder or Snap to create control program(s) for your UC Open.
2
If applicable, print the Sequence of Operation, which includes the points list.
NOTE You can create a points list under Reports in the i-Vu® application or Field Assistant after installing
your control program.
This Installation Guide
1
Prepare a wire list using the points list. Refer to Appendix A (page 23).
2
Use the wire list and the following installation procedures to install and wire I/O points to your UC Open.
The i-Vu® or Field Assistant application
1
Upload the controller to the database by selecting the router in the navigation tree.
2
Select Devices > Manage tab.
UC Open
Installation and Start-up Guide
16
CARRIER CORPORATION ©2019
All rights reserved