Safety Considerations - Carrier UC Open Installation And Startup Manual

Table of Contents

Advertisement

Environmental operating
range
Storage temperature range
Physical
Overall dimensions
Mounting dimensions
Panel depth
Weight
BACnet support
Listed by

Safety considerations

WARNING Disconnect electrical power to the UC Open before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
UC Open
Installation and Start-up Guide
0 to 130°F (-18 to 54°C), 0 to 90% relative humidity, non-condensing
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Rugged GE C2950HF Cycoloy plastic
A:
5-5/8 in. (14.3 cm)
B:
5-1/8 in. (13 cm)
C:
5-1/4 in. (13.3 cm)
D:
2-9/16 in. (6.5 cm)
E:
3/16 in. (.5 cm)
2 in. (51 mm)
0.6 lbs (0.27 kg)
Conforms to the BACnet Advanced Application Controller (B-AAC) Standard
Device Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex
L, Protocol Revision 9
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
3
Introduction
CARRIER CORPORATION ©2019
All rights reserved

Advertisement

Table of Contents
loading