5.2 Regulation section
5.2.1 Removing the terminal cover
When removing the covers be carefull to lateral metal sheet enclosure. Presence of
sharp edge are possible.
Warning!
5.2.2 Cable Cross Section
Terminal strips
(Regulation card)
5.2.3 Regulation section connection
For shielding of the regulation section (recommended), fasten the shield of the
cables to the omega sections (see fi gure above).
34
A
Maximum Cable Cross Section
(mm
)
(AWG)
2
0.2 ... 2.5
24 ... 12
Figure 5.2.3.1: Regulation shielding
ADV200 • Quick start up guide - Specification and installation
A
Recommended
stripping
(mm)
7
Tightening torque (min)
(min)
(Nm)
0.5