Troubleshooting
Chapter 4 provides information to guide the user in
troubleshooting the 1336 REGEN Line Regeneration Package.
Included is a listing and description of the various faults that can
occur and their code numbers as they would appear on the HIM.
An additional section is included to document troubleshooting
from the 1336 REGEN Converter Control Board. (3) LEDs on the
Control Board provide status and fault information for the 1336
REGEN Line Regeneration Package.

Clearing a Fault

When a fault occurs, the Enable
change state and the 1336 REGEN Converter will shut down. Issu-
ing a reset command will clear the fault and reset the converter.
When a fault occurs however, the cause should be investigated and
action taken prior to resetting the fault.

1336 REGEN Converter Control Board LED Indication

LED
Status
Indicates
Off
No Faults Exist
FAULT
On
A Fault Has Occurred — Refer to the Fault Codes Below
DS1
Off
No Power Has Been Applied to the Converter
ENABLE
On
The Converter Is Being Powered Up
DS2
On Flashing The Converter Has Tripped — Refer to the Fault Codes Below
Off
The Converter Is Not Enabled
STATUS
On
The Converter Is Enabled
DS3
On Flashing The Converter Has Tripped — Refer to the Fault Codes Below
Off
The Converter Is Not Enabled
COM
On
A host checksum has occurred.
DS4
2 Flashes
On
Continuous
The Converter Has Tripped — Refer to the Fault Codes Below
Flashing
Chapter
Fault Output Relays will
&
4