Grounding; Sensitive Circuits; Te (True Earth) Termination; Pe (Power Earth) Termination - Allen-Bradley 1336 REGEN Series User Manual

Line regeneration package
Table of Contents

Advertisement

380-480VAC Power
Wiring

Sensitive Circuits

It is essential to define paths
through which high frequency
ground currents flow to ensure that
sensitive circuits do not share a
path with these currents. Control
and signal conductors should not
be run near or parallel to power
conductors.

TE (True Earth) Termination

The converter's TE terminals are
used for all control signal shields
internal to the 1336 REGEN
Converter and must be connected
to the converter's TE
terminals by a separate
continuous lead.
D Frame
USE 75° C COPPER WIRE ONLY

PE (Power Earth) Termination

A safety ground is required by
code. This point must be
connected to adjacent building
steel or a floor ground rod
provided grounding points comply
with NEC and local regulations.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Grounding

All 1336 REGEN components must be connected to system
ground at the PE power ground terminal provided. Ground
impedance must conform to the requirements of national and local
industrial safety regulations (NEC, CENELEC, etc.), and should
be inspected and tested at appropriate intervals. In any cabinet, a
single low-impedance ground point or ground bus bar should be
used. All circuits should be grounded independently and directly.
The AC supply ground conductor should also be connected
directly to this ground point or bus bar.
Conduit/4-Wire Cable
Building Structure Steel
1
1
PE
PE
TE
DC+
DC–
R2
S2
T2
TORQUE TERM. TO 6 N-m (52 lb-in)
(2) jumpers connect PE and TE at the 1336 REGEN
1
Converter Main Terminal Block. Consult
Allen-Bradley Application Engineering prior
to removing either jumper.
Fig re 3 4 — Regenerative Brake Gro nding
Regenerative Brake Operation
GND
USER
SUPPLIED
120V AC
Nearest
AC DRIVE
PE
Important: If you are using a Regenerative Brake with a B Frame
2
AC drive, refer to the Power-up Sequence on page 3-3.
3–11
R
S
1336 REGEN
Precharge
T
PE
TB1-1
TB1-3
R1
S1
T1
PE
GND
A1
B1
C1
1321 3%
Line Reactor
A2
B2
C2
GND
PE
R2
S2
T2
1336 REGEN
120 RTN
Converter
120V AC
1
PE
TE
PE
+DC
–DC
–DC
+DC
PE
2