FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules
Catalog Numbers 5094-IY8, 5094-IY8XT
Topic

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic
Product Overview
The 5094-IY8 and 5094-IY8XT analog 8-channel universal input modules offer single-ended differential, non-isolated input channels as well as Thermocouple and RTD input
channels that can operates in a wide range of applications. The modules can operate in multiple input ranges based on the input type that is connected to the modules.
FLEX 5000® I/O modules use the Producer-Consumer communication model. The Producer-Consumer communication model is an intelligent data exchange between modules and
other system devices in which each module produces data without first being polled.
FLEX 5000 I/O modules are used with some Logix 5000® controllers and configured with the Studio 5000 Logix Designer® application. For more information on how which Logix
5000 controllers and Logix Designer application versions are compatible with FLEX 5000 I/O modules, see the publications listed in
Page
1
5
5
5
7
7
8
9
9
12
13
13
13
14
Page
1
3
3
4
9
13, 14
Additional Resources on page
14.

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley FLEX 5000 5094-IY8

  • Page 1: Table Of Contents

    Installation Instructions Original Instructions FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Catalog Numbers 5094-IY8, 5094-IY8XT Topic Page Summary of Changes About the Module Before You Begin Required Components Install the Module Install the End Cap Wire the Terminal Base Disconnect Wires from the Terminal Base Wiring Diagram Power the System Remove the Module...
  • Page 2 FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
  • Page 3: Updated Uk And European Hazardous Location Approval

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
  • Page 4: Updated Special Conditions For Safe Use

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions WARNING: Special Conditions for Safe Use: • This equipment is not resistant to sunlight or other sources of UV radiation. • This equipment shall be mounted in an UKEX/ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with EN/IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments.
  • Page 5: About The Module

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions About the Module FRONT VIEW BACK VIEW Release lever Keyswitch ports FLEX 5000 Module status indicator Module power Slide-in writable label I/O status indicators Latching hooks Before You Begin Before you install the module, you must install a FLEX 5000 I/O system. At minimum, the system must include a FLEX 5000 EtherNet/IP™ adapter and backplane end cap. For more information on how to install a FLEX 5000 I/O system, see the FLEX 5000 EtherNet/IP Adapter Installation Instructions, publication 5094-IN001, and the FLEX 5000 Terminal Base Assembly Modules Installation Instructions, publication 5094-IN010.
  • Page 6 1770-4.1 for more information. You can use a zinc-plated chromated steel DIN rail such as the Allen-Bradley® 199-DR1; 46277-3; EN60715 – 35 x 7.5 mm (1.38 x 0.30 in.) with your FLEX 5000 I/O system. Power Considerations ATTENTION: Power to this equipment and all connected I/O must be supplied from a source compliant with the following: Isolated from Mains power via an approved Isolating Transformer constructed with Basic Insulation.
  • Page 7: Install The Module

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions Install the Module WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electric arcing causes excessive wear to contacts on both the module and its mating connector.
  • Page 8: Wire The Terminal Base

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions Align the end cap with interlocking pieces on the last terminal base in the system. Push the end cap towards the DIN rail. Press the locking tab until it clicks. Wire the Terminal Base WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur.
  • Page 9: Disconnect Wires From The Terminal Base

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions Disconnect Wires from the Terminal Base WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
  • Page 10 FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions These examples apply to the 5094-IY8 and 5094-IY8XT analog input modules when used in voltage mode. 5094-IY8 and 5094-IY8XT Wiring Diagram – 2-wire Voltage Mode 0+ 0- 3+ 3- 4+ 4- 5+ 5- 2-wire –...
  • Page 11 FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions These examples apply to the 5094-IY8 and 5094-IY8XT analog input modules when used in RTD mode. 5094-IY8 and 5094-IY8XT Wiring Diagram – 2-wire RTD Mode 0+ 0- 2+ 2- 3+ 3- 4+ 4- 5+ 5- 2-wire...
  • Page 12: Power The System

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions This example applies to the 5094-IY8 and 5094-IY8XT analog input modules when used in thermocouple mode. 5094-IY8 and 5094-IY8XT Wiring Diagram – Thermocouple Mode 0+ 0- 2+ 2- 3+ 3- 4+ 4- 5+ 5- Thermocouple/ mV source...
  • Page 13: Remove The Module

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions Remove the Module WARNING: When you insert or remove the module while backplane power or SA power (field-side) is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 14: Additional Resources

    FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions 5094-IY8 and 5094-IY8XT Analog 8-channel Current/Voltage/RTD/Thermocouple Input Module Specifications (Continued) Attribute Value 0.34… 2.5 mm (22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Wire size Ferrule according to DIN 46 228/1.
  • Page 15 FLEX 5000 Analog 8-channel Current/Voltage/RTD/Thermocouple Input Modules Installation Instructions Notes: Rockwell Automation Publication 5094-IN008D-EN-P - August 2022...
  • Page 16 Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Connect with us. Allen-Bradley, expanding human possibility, FactoryTalk, FLEX 5000, Logix 5000, Rockwell Automation, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.

This manual is also suitable for:

Flex 5000 5094-iy8xt

Table of Contents