Allen-Bradley 1336 REGEN Series User Manual page 90

Line regeneration package
Table of Contents

Advertisement

Programming
B
O V S
W
T r i p
1 6
1
3
0 %
Parameter No.
Display Units
Read/Write
Parameter Type
130% DC
Factory Default
BASE
120/135% DC
Min/Max Value
BASE
100 = 4096
Drive Units
B
U V S
W
T r i p
1 7
6
0 %
Parameter No.
Display Units
Read/Write
Parameter Type
60% DC
Factory Default
BASE
50/100% DC
Min/Max Value
BASE
100 = 4096
Drive Units
L
O V T
r
i p 1
1
1
5 %
1 8
Parameter No.
Display Units
Read/Write
Parameter Type
115% AC
Factory Default
BASE
110/130% AC
Min/Max Value
BASE
100 = 4096
Drive Units
L
O V T
r
i p 2
1
3
0 %
1 9
Parameter No.
Display Units
Read/Write
Parameter Type
130% AC
Factory Default
BASE
120/135% AC
Min/Max Value
BASE
100 = 4096
Drive Units
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
DC Bus Overvoltage Trip Level
This parameter sets the software over voltage trip point of the DC bus. The 1336 REGEN
Converter is factory set to prevent it from operating when DC bus voltage is 30% above
DC
volts.
BASE
16
For 380VAC input Line Regeneration Packages, DC
%
For 460VAC input Line Regeneration Packages, DC
DC Bus Undervoltage Trip Level
This parameter sets the software under voltage trip point of the DC bus. The 1336 REGEN
Converter is factory set to prevent it from operating when DC bus voltage is less than 60% of
DC
volts.
BASE
17
For 380VAC input Line Regeneration Packages, DC
%
For 460VAC input Line Regeneration Packages, DC
AC Line Overvoltage Trip Level 1 (Not Enabled)
This parameter sets a software over voltage trip point that is active when the 1336 REGEN
Converter is not enabled. The 1336 REGEN Converter is factory set to prevent it from being
enabled when the input AC line voltage is 15% above the AC
18
For 380VAC input Line Regeneration Packages, AC
%
For 460VAC input Line Regeneration Packages, AC
Important: The 1336 REGEN Converter cannot be enabled for the [LOV Trip 1] to be
changed.
AC Line Overvoltage Trip Level 2 (Enabled)
This parameter sets a second software over voltage trip point that is active when the 1336
REGEN Converter is enabled. The 1336 REGEN Converter is factory set to trip if the input AC
line voltage is 30% above the AC
19
For 380VAC input Line Regeneration Packages, AC
%
For 460VAC input Line Regeneration Packages, AC
Important: The 1336 REGEN Converter cannot be enabled for the [LOV Trip 2] to be
changed.
Regenerative Brake Operation
volts = 537V.
BASE
volts = 650V.
BASE
volts = 537V.
BASE
volts = 650V.
BASE
volts.
BASE
volts = 380V.
BASE
volts = 460V.
BASE
volts.
BASE
volts = 380V.
BASE
volts = 460V.
BASE
3–37