Protection - Allen-Bradley 1336 REGEN Series User Manual

Line regeneration package
Table of Contents

Advertisement

B–2
Specifications

Protection

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Regenerative DC Bus Supply Mode
Only
Bus Overvoltage Trip
Bus Undervoltage Trip
Nominal Bus Voltage
AC Input Overvoltage Trip
Heatsink Over Temperature Trip
1336R Converter Overcurrent Trip
Software Overcurrent Limit
Hardware Overcurrent Limit
Line Transients
Up to 6000 Volts Peak per ANSI C62.41-1991
Control Logic Noise Immunity
Showering Arc Transients Up to 1500 Volts Peak
Power Ride-Thru
6 mSec. at Full Load
Control Logic Ride-Thru
0.5 Sec. Minimum, 2 Sec. Typical
380VAC Input
480VAC Input
670VDC
850VDC
430VDC
520VDC
610VDC
735VDC
Factory Set to +15% of Nominal Line
Voltage
100˚C
Factory Set to 192% of AC Input Current
Factory Set to 245% of AC Input Current