Allen-Bradley 1336 REGEN Series User Manual page 88

Line regeneration package
Table of Contents

Advertisement

Programming
B
u s V
o
l t s A c t .
5
7 3 5
.
0 V O L T
Parameter No.
Volts
Display Units
Read Only
Parameter Type
1 = 0.1V
Drive Units
C
o n d
A
n g l e C o n s t
0 .
5
0
9
Parameter No.
Number
Display Units
Read/Write
Parameter Type
Factory Default
0.50/0.55
Min/Max Value
1.00 = 4096
Drive Units
S
h i f t
A n g l C o n s t
0 .
0
3
1 0
Parameter No.
Number
Display Units
Read/Write
Parameter Type
Factory Default
0.00/0.06
Min/Max Value
1.00 = 4096
Drive Units
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Actual Bus Voltage
Displays the actual voltage on the DC bus in DC volts.
5
Conduction Angle Constant
Altering this parameter allows the conduction angle of the Regenerative Brake — The
duration of IGBT device conduction per period — to be tuned while the 1336 REGEN
Converter is enabled.
9
Example:
For a setting of
For a setting of
0.50
Reducing the [Cond Angle Const] increases the conduction angle. A larger conduction angle
yields higher Regenerative Brake efficiency, since regeneration for the utility cycle lasts longer.
A larger conduction angle however, also causes higher no-load quiescent currents.
Increasing the [Cond Angle Const] decreases the conduction angle, while slightly increasing
DC bus voltage and reducing no-load quiescent currents.
Shift Angle Constant
Altering this parameter allows the conduction angle of the Regen Brake to be adjusted relative
to the reference point of 30˚, after zero crossing of the phase voltage.
10
The default factory setting of
conditions.
0.03
For a setting of
current will initially rise slowly, then increase quickly at the conduction period. The resultant
current waveform for a fully loaded unit during regeneration will be more triangular.
Increasing the setting to
DC bus voltage. At the beginning of conduction period, input line current will initially rise
quickly, then increase slowly. The resultant current waveform for a fully loaded unit during
regeneration will now be more rectangular.
Regenerative Brake Operation
0.5
, the conduction angle has a maximum value of 120˚.
0.55
, the conduction angle is at it's minimum value, 113˚.
0.03
should be adequate for the majority of line and load
0
, IGBT quiescent current will be minimal. During regeneration, Input line
0.06
will result in increasing the quiescent current and reducing the
3–35