BACnet/IP
2-3
CONNECTING TO THE REMOTE USER INTERFACE
Start the Remote User Interface (RUInet) by placing the mouse pointer on the "Remote User
Interface" icon and double-clicking. The following screen will appear:
Note: You will see reference to the third-party manufacturer's name for the BACnet Interface
Module, "ProtoNode", throughout the Remote User Interface utility.
2-4
USING THE REMOTE USER INTERFACE TO SET IP ADDRESS
1. From the Main Menu, press "I — Change IP Address" to enter the Edit IP Address Set-
tings menu.
2. Press "1" to modify the IP address of the Ethernet adapter.
3. Type in a new IP address in the format 192.168.2.X and press <Enter>.
4. If necessary, press "2" to and change the Subnet mask.
5. Type in a new Subnet Mask and press <Enter>.
6. If necessary, press "3" to and change the IP Gateway.
7. Type in a new IP Gateway and press <Enter>.
Note: If the BACnet Interface Module is connected to a router, the IP Gateway of the mod-
8. Reset the BACnet Interface Module by selecting "! — Restart FieldServer". Updated
settings only take effect after a system restart.
9. Close the Remote User Interface utility.
10. Unplug the Ethernet cable from the PC/laptop and connect it to the network hub or router.
June 2012
Figure 2-2. RUInet Main Menu
ule should be set to the IP address of the router that it is connected to.
2-2
P/N 06-237214-002