General Information
1-3.2
DIP Switches
Three banks of DIP Switches are located on the Main Board. Refer to Figure 1-5 below:
Note: When setting DIP switches, ensure that power to the board is OFF.
Switches A0 through A7
(set at the factory to an address
value of "8"
– refer to Table 3-1
to change address value for use
with BACnet MS/TP, if applicable
• "A Bank" Switches — Store the Address to set Node-ID/Device Instance. Default is "8".
Refer to Table 3-1 in Chapter 3 of this manual for switch settings.
• "B Bank" Switches — Store the serial Baud Rate. Default is 38,400 baud, set at the
factory. Refer to Table 1-1 below. For MS/TP use, this value must be set to the baud rate
of your MS/TP network.
• "S Bank" Switches — Store the Settings from a group of pretested/preloaded
configuration files which are stored in the BACnet Interface Module.
shown in Table 1-2 below. This value is set at the factory and should only be changed if
an Add-On BACnet Interface Module is installed (Switch S0 only).
Note: A single BACnet Interface Module supports systems with up to 4 Signaling Line
BACnet Interface Module (SLC Loop 1 - 4)
Add-On BACnet Interface Module (SLC Loop 5 – 8)
June 2012
)
Figure 1-5. BACnet Interface Module DIP Switches
Table 1-1. "B Bank" DIP Switch Settings
Circuits (SLCs). For systems including more than 4 SLCs, an Add-On BACnet
Interface Module is required.
Table 1-2. "S Bank" DIP Switch Settings
Configuration
Switches B0 through B3
(set at the factory to a value of "38400";
refer to Table 1-1 to set value to your
BACnet MS/TP network baud rate, if applicable)
Switches S0 through S3
(S0 should be set to OFF on topmost module
and set to ON on optional Add-On module)
Baud
B0
B1
B2
9600
On
On
On
19200
Off
Off
Off
38400
On
On
Off
57600
Off
Off
On
76800
On
Off
On
1-6
B3
Off
On
On
On
On
Default settings are
S Bank DIP Switches
S0
S1
S2
Off
Off
Off
On
Off
Off
P/N 06-237214-002
S3
Off
Off