General Information
1-6
STATUS DATA MAPPING
The ARIES NETLink control unit statuses are mapped to BACnet Event States as shown in
Table 1-6 below:
1-6.1
Systems With 4 Or Fewer SLCs (One BACnet Interface Module)
For a ARIES NETLink system with 4 or fewer Signaling Line Circuits (SLCs), the control unit
data is mapped to BACnet Multi-State Inputs as shown in Table 1-7 below:
Table 1-7. BACnet Multi-State Input Mapping for ARIES NETLink Systems With 4 or Fewer SLCs
June 2012
Table 1-6. BACnet Event State Mapping for ARIES NETLink
Control Unit Status
Supervisory
Trouble
Pre-Alarm
Alarm
Normal
Control Unit Data
System Status
SLC Loop 1 - Device 0
1
255
SLC Loop 2 - 0
255
SLC Loop 3 - 0
255
SLC Loop 4 - 0
255
Reserved Registers
C Variable 1
C Variable 50
BACnet Object Event State
0x1; fault
0x1; fault
0x1; fault
0x2; in_alarm
0
Multi_State_Input
0
1
2
256
257
512
513
768
769
1024
1025 - 1151
1152
1201
1-10
P/N 06-237214-002