Chapter 3 Bacnet Ms/Tp; Bacnet Interface Module Addresses; Default Address Value; Changing Address Value - UTC Fire and Security KiddeFire Systems ARIES NETLink BACnet User Manual

Interface module
Table of Contents

Advertisement

3-1

BACNET INTERFACE MODULE ADDRESSES

When interfacing the BACnet Interface Module with a BACnet MS/TP network, the module
address must be physically set by moving a series of DIP switches. Refer to Figure 1-4 in
Chapter 1, General Information, for location of the "A Bank" (Address) DIP switches.
Note: When setting DIP switches, ensure that power to the board is OFF.
3-1.1

Default Address Value

Note that all BACnet Interface Modules are factory-set to the address of "8" when shipped.
(The default value is shown in a yellow highlighted row in Table 3-1.)
3-1.2

Changing Address Value

To change the module's address from its default setting, move the "A Bank" dip switches to
the corresponding ON/OFF positions for the desired address value. Refer to Table 3-1 for a
list of available addresses and how to position them.
3-2

BAUD RATE

Refer to Table 1-1 in Chapter 1, General Information, to set to the module's serial baud rate
to the baud rate of your MS/TP network by positioning the "B Bank" DIP switches. Note that
the default is 38,400 baud, set at the factory.
P/N 06-237214-002
CHAPTER 3
BACNET MS/TP
3-1
BACnet MS/TP
June 2012